Specifications

ClimateMaster Water-Source Heating and Cooling Systems
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Tranquility Vertical Stack (TRM) Series
Rev.: 05/23/07D
TRM
44
Slab Slot Chart - 3 Pipe
To use this chart look down the model column to nd the model. Then look across to nd the clear height. If your
clear height exceeds 96" use the 96" slab slot size. Then under the type of installation read the slab slot size.
Above charts allow 1" tolerance in clear height to allow for variance in oor to oor dimensions.
Clear height is the oor to oor dimension of the oor the unit is on minus the slab thickness above.
3 Pipe Standard 88" Cabinet
Slot Width
Slot Length
Clear Height = FF - Slab Thickness
Model
TRM
Clear
Height
Slab Slot Size
Type of Installation
Type 1 Type 2 Type 3
W x L
W x L
W x L
09 - 12
96
95
94
93
92
5 7/8" X 15" [149 X 381]
6 1/4" X 15" [159 X 381]
6 5/8" X 15" [168 X 381]
7" X 15" [179 X 381]
7 1/2" X 15" [191 X 381]
5 7/8" X 15" [149 X 381]
5 3/8" X 15" [137 X 381]
5 3/8" X 15" [137 X 381]
Not Recommended
Not Recommended
5" X 15" [127 X 381]
5" X 15" [127 X 381]
5" X 15" [127 X 381]
5" X 15" [127 X 381]
Not Recommended
15 - 18
96
95
94
93
6 1/4" X 18" [159 X 457]
6 3/4" X 18" [171 X 457]
7 1/8" X 18" [181 X 457]
7 5/8" X 18" [194 X 457]
5 1/8" X 18" [130 X 457]
5 3/8" X 18" [137 X 457]
Not Recommended
Not Recommended
5" X 18" [127 X 457]
5" X 18" [127 X 457]
5" X 18" [127 X 457]
5" X 18" [127 X 457]
24 - 36
96
95
94
7" X 22" [178 X 559]
7 1/2" X 22" [191 X 559]
8" X 22" [203 X 559]
5 1/8" X 22" [130 X 599]
Not Recommended
Not Recommended
5" X 22" [149 X 599]
5" X 22" [149 X 599]
5" X 22" [149 X 599]
09 - 12 91 or less Not Recommended Not Recommended Not Recommended
15 - 18 92 or less Not Recommended Not Recommended
5" X 18" [149 x 457]
24 - 36 93 or less Not Recommended Not Recommended
5" X 22" [127 x 599]