Specifications
TRM
43
www.climatemaster.com
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Tranquility Vertical Stack (TRM) Series
Rev.: 05/23/07D
Cabinet Height & Slab Slot Size
To determine the slab slot size required for the risers and to determine if clear height is OK for unit installation, use
the cabinet height and slab slot charts on the next page.
To use the charts you will need the clear height in the room the unit is in, size of unit, number of risers, riser di-
mensions and type of installation. (See below)
If any clear height is less than 96" (2438) check the minimum cabinet height and slot size chart to determine if the
size unit you need will fi t. If the standard 88" (2235) cabinet does not fi t check the short 80" (2032) cabinet height
and slot size chart. Call the factory if the short 80" (2032) cabinet does not fi t. Check with the contractor for OK to
use 80" (2032) cabinet.
Clear Height (swing height) = Floor to Floor Dimensions - Slab Thickness of Slab above the unit. CH = FF - ST.
Type 1 Single Units
With a minimum clear height of 94" (2388). Start with the unit
lying on the chase.
Type 2 Single Units
With a minimum clear height of 96" (2438). Start with the unit
lying with the chase on top.
Type 3 Single
With a minimum clear height of 94" (2388). Start with the unit
lying on its side as shown.