Riser Length Sizing
To determine the riser tail piece length of a unit (unit "A").
Riser Tail Piece ( of unit A)= FF - RRH + 2" (51).
RRH: Room riser height is cabinet height + 3" (76).
Standard cabinet height is 88" (2235).
RRH= 88" (2235) + 3" (76) = 91" (2311).
FF: Floor to Floor height is the dimension from the top of the
slab above to the top of the slab below.
To determine the riser tail piece length of a unit (unit "B") that will
require riser extensions to a unit below.
Minimum Tail Piece Length (of unit "B") = slab thickness + 5" (127).
To determine riser extensions lengths see page Riser Extension Sizing.
Note: If riser length exceeds 115" (2921), riser extensions must be
used. See Riser Extension Sizing. The riser tail piece must extend
through the slab a minimum of 5" (127) to facilitate brazing. Special
care must be taken in sizing riser lengths and tail piece lengths when:
A) Riser extensions are used.
B) Floor to oor heights vary.
C) Slab thickness varies from oor to oor.
See Riser Arrangement for selection of top oor riser applications.