Specifications
ClimateMaster Water-Source Heating and Cooling Systems
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Tranquility Vertical Stack (TRM) Series
Rev.: 05/23/07D
TRM
38
Riser Tailpiece (length of riser that extends down from cabinet bottom) -
Dimension F on submittal drawing- Riser tailpiece sized for 2" (51) insertion into 3" (76) expanded section at top
of cabinet. Actual job fi t may be 1" (25) to 3" (76) insertion (built-in +1" (25) fl oor to fl oor tolerance). Riser tailpiece
should extend beneath bottom of slab a minimum of 5" (127) to facilitate brazing.
3" Expanded Section - Riser expanded at top of unit to accept a pipe diameter from unit above. (Top of riser
always 3" (76) above top of unit.)
Floor to Floor Height (FF dim.) - Dimension from top of
unit slab to top of slab above.
Slab Thickness (ST dim.) - Includes basic slab thickness
plus any material added to slab prior to setting cabinets.
Clear Height (Top of unit slab to bottom of slab above)
- This dimension is used to determine whether cabinet-
riser assembly will pivot through slab core without hitting
bottom of slab above unit. If selected cabinet-riser will
not pivot into position, special riser extension or shorter
cabinet will have to be considered, (Clear height = fl oor
to fl oor dimension less thickness of slab above unit.)
Room Riser Height (cabinet height + 3" (76) - Standard
cabinet height (88"(2235)) + 3" (76) = 91" (2311) -
Shorter than standard cabinet heights will have shorter
room riser heights.
Maximum Riser Height - Maximum length is 115" (2921).
Total Riser Height (dim. L on submittal) - Room riser
(RRH) height + riser tailpiece length (F) = total riser
length (115" (2921) max.).
Total Riser Height = Floor to Floor + 2" (51)
(115" (2921) max.).
Slab thickness (ST) (slab above)
3 " (76)
Slab thickness (ST) (slab below)
Clear
Height
Floor to
Floor
Height (FF)
Room Riser
Height
(RRH)
Cabinet
Height
Total Riser
Height (L)
(115” Max.)
(2921)
Riser Tailpiece (F)
Riser Defi nitions