Instruction manual
THE SMART SOLUTION FOR ENERGY EFFICIENCY
W (ERV) Series
Rev.: 15 May, 2015
3
climatemaster.com
Installation
1.  Attach duct work to duct fl anges on ERV.
2.  Remove ERV control access panel to connect fi eld 
wiring.
3.  Route class II low voltage wire (3 conductor) from 
thermostat or energy management through small 
bushing in end panel of ERV. See wiring diagram.
a. Thermostat (dependent) - connect in parallel at 
rooftop unit with “G”, “C” and “W”. Then connect 
matching color at terminal 1, 2, and 3 respectively 
on ERV circuit board.
b. Energy Management - provide +24 VAC to “1” and 
common, 24 VAC to “2’ terminals on ERV circuit 
board.
c. Thermostat (dedicated) - splice into +24 vac 
(blue wire) at (control circuit board) transformer 
connection run wire to “R” terminal. Then run 
another wire from “G” terminal to ERV (control 
circuit board) terminal block #1.
4.  All electrical connections must conform to any local 
codes and current National Electric Codes (NEC) and 
Canadian Electric Codes (CEC). Refer closely to unit 
wiring diagram in unit and/or in these instructions for 
proper wiring connections.
5.  Refer to the unit nameplate for minimum circuit 
ampacity (MCA) and maximum overcurrent protection 
size (fuse).
6.  Electrical data is listed on unit rating plate and motor 
name plates.
7.  Connect line voltage power supply to ERV fuse block 
in control box of unit from disconnect switch. See 
wiring diagram.
 CAUTION! 
CAUTION! Blower speed must be adjusted for the given 
external static pressure and airfl ow (CFM) requirements. If 
blower speed is not adjusted for conditions, possible motor 
over loading can occur.
8.  Ground unit with a suitable ground connection either 
through unit supply wiring or an earth ground.
NOTE: Unit voltage entries must be sealed 
weather tight after wiring is complete.
9.  Remove motor access panels. Locate belts fastened 
to blower assembly. Install belt onto motor and blower 
pulley. Adjust motor sheave to correct blower RPM for 
CFM and external static pressure requirements. See 
charts in this instruction. Multiple pulley arrangements 
are available to meet the entire range.
10. Replace access panel onto the ERV unit and secure.
11. Restore power to unit.
12. Cleanup once unit is operating properly, caulk 
any open joints, holes or seams to make the units 
completely air and water tight.
13. Leave this instruction manual with owner or in an 
envelope to be kept near unit.
Operation
(How It Works)
The unit contains an Energy Recovery Wheel (ERW) 
that is a new concept in rotary air-to-air heat exchangers. 
Designed as a packaged unit for ease of installation and 
maintenance, only the connection of electrical power is 
required to make the system operational.
When slowly rotating through counter fl owing exhaust 
and fresh air streams the ERW adsorbs sensible heat 
and latent heat from the warmer air stream and transfer 
this total energy to the cooler air stream during the 
second half of its rotating cycle. Rotating at 50-60 
revolutions per minute, the wheel provides constant fl ow 
of energy from warmer to cooler air stream. The large 
energy transfer surface and laminar fl ow through the 
wheel causes this constant fl ow of recovered energy 
to represent up to 85% of the difference in total energy 
contained within the two air streams.
Sensible and latent heat are the two components of total 
heat. Sensible heat is energy contained in dry air and 
latent heat is the energy contained within the moisture 
of the air. The latent heat load from the outdoor fresh air 
on an air conditioning system can often be two to three 










