Tranquility® 22 Digital (TZ) Series Submittal Data Models TZH/V 024 - 060 60Hz - HFC-410A English Language/I-P Units SUBMITTAL DATA - I-P UNITS Unit Designation: Job Name: Architect: Engineer: Contractor: PERFORMANCE DATA Cooling Capacity: Btuh EER: Heating Capacity: Btuh COP: Rev.
Tranquility® 22 Digital (TZ) Series Submittal Data Models TZH/V 024 - 060 60Hz - HFC-410A English Language/S-I Units SUBMITTAL DATA - S-I UNITS Unit Designation: Job Name: Architect: Engineer: Contractor: PERFORMANCE DATA Cooling Capacity: kW EER: Heating Capacity: kW COP: Rev.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P Table of Contents *Page Number Unit Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 iGate™ Communicating Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 vFlow™ Internal Variable Water Flow Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Selection Procedure . . . . . . . . . . . . . . . . . . . .
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P Unit Features THE TRANQUILITY® 22 TWO-STAGE (TZ) SERIES The TZ comes with all the reliability features the ClimateMaster Tranquility® Series is known for. They include superb efficiency ratings, quiet operation and application flexibility. Tranquility® 22 units are available in vertical upflow and horizontal configurations in capacities of 24, 30, 36, 42, 48, and 60 Mbtuh.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P Unit Features UNIT FEATURES • Sizes 024 (2 ton, 7.0 kW) through 060 (5 tons, 17.6 kW) • EarthPure® (HFC-410A) refrigerant • Copeland UltraTech™ two-stage unloading scroll compressors • ECM variable speed fan motor with soft start • DXM2 two-way communicating controller • Exceeds ASHRAE 90.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P iGate™ Communicating Controls iGate™ Information gateway to monitor, control and diagnose your system Tranquility® 22 is equipped with industry-first, iGate™ – Information Gateway – 2-way communicating system that allows users to interact with their system in plain English AND delivers improved reliability and efficiency by precisely controlling smart variable speed components.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P vFlow™ Internal Variable Water Flow Control vFlow™ Internal Variable Water Flow Industry-first, Built-in vFlow™ replaces a traditionally inefficient, external component of the system (water circulation) with an ultra-high-efficient, variable speed, internal water flow system. This saves 70-80% on operating water circulator vs traditional single speed pump systems.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P Selection Procedure Reference Calculations Heating Cooling LWT = EWT - HE GPM x 500 LWT = EWT + LAT = EAT + HC CFM x1.08 LAT (DB) = EAT (DB) - HR GPM x 500 LC = TC - SC SC CFM x1.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P Selection Procedure Step 1 Determine the actual heating and cooling loads at the desired dry bulb and wet bulb conditions. Example Equipment Selection For Cooling Step 2 Obtain the following design parameters: Entering water temperature, water flow rate in GPM, air flow in CFM, water flow pressure drop and design wet and dry bulb temperatures. Air flow CFM should be between 300 and 450 CFM per ton.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P TZ Series Nomenclature 1 2 3 4 5 6 7 TZ V 024 C G D 3 8 9 10 11 12 13 14 15 5 B L T S STANDARD SERIES S = Standard TZ = Tranquility® 22 SUPPLY AIR FLOW & MOTOR CONFIGURATION CONFIGURATION V = Vertical Up H = Horizontal T B S UNIT SIZE Supply Configuration Top TZV TZH Back TZH Straight Motor ECM ECM ECM RETURN AIR FLOW CONFIGURATION 024 030 036 042 048 060 L = Left Return R = Right Return V = Left Return, Stainless Steel Drain Pan W
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data AHRI/ASHRAE/ISO 13256-1 ASHRAE/AHRI/ISO 13256-1. English (I-P) Units Water Loop Heat Pump Cooling 86°F Model Ground Water Heat Pump Heating 68°F Cooling 59°F Ground Loop Heat Pump Heating 50°F Part Cool 68°F Full Heat 32°F Part Heat 41°F Capacity EER Btuh Btuh/W Capacity COP Btuh Capacity Btuh EER Btuh/W Capacity Btuh COP Capacity Btuh EER Btuh/W 18,100 16.1 20,600 5.2 20,300 27.2 16,700 4.4 19,400 22.2 14,700 4.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TZ H/V 024 (Part Load) with Modulating Valve or Variable Speed Pump 600 CFM Nominal (Rated) Airflow Cooling,600 CFM Nominal (Rated) Airflow Heating WPD EWT °F GPM 20 30 40 50 60 70 80 90 100 110 120 Performance capacities shown in thousands of Btuh COOLING - EAT 80/67°F WPD kW HR EER LWT HWG Cap 0.7 22.4 15.2 0.71 24.9 31.6 60.0 0.9 0.6 22.4 15.2 0.71 24.9 31.6 60.0 0.9 0.3 0.6 22.4 15.2 0.71 24.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TZ H/V 024 (Full Load) with Modulating Valve or Variable Speed Pump 750 CFM Nominal (Rated) Airflow Cooling, 750 CFM Nominal (Rated) Airflow Heating WPD EWT °F GPM 20 30 40 50 60 70 80 90 100 110 120 Performance capacities shown in thousands of Btuh COOLING - EAT 80/67°F WPD PSI FT TC SC kW HR EER LWT HWG Cap GPM 1.7 0.7 1.5 29.3 19.2 1.18 33.3 24.9 60.0 1.3 2.2 0.6 1.4 29.3 19.2 1.18 33.3 24.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TZ H/V 030 (Part Load) with Modulating Valve or Variable Speed Pump 750 CFM Nominal (Rated) Airflow Cooling, 750 CFM Nominal (Rated) Airflow Heating WPD EWT °F GPM 20 30 40 50 60 70 80 90 100 110 120 Performance capacities shown in thousands of Btuh COOLING - EAT 80/67°F WPD HR EER LWT HWG Cap GPM 2.8 26.5 17.4 0.96 29.8 27.6 60.0 1.0 2.4 26.5 17.4 0.96 29.8 27.6 60.0 1.0 1.0 2.4 26.5 17.4 0.96 29.8 27.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TZ H/V 030 (Full Load) with Modulating Valve or Variable Speed Pump 900 CFM Nominal (Rated) Airflow Cooling, 900 CFM Nominal (Rated) Airflow Heating WPD EWT °F GPM 20 30 40 50 60 70 80 90 100 110 120 Performance capacities shown in thousands of Btuh COOLING - EAT 80/67°F WPD EER LWT HWG Cap GPM 3.4 34.7 21.5 1.51 39.8 23.0 60.0 1.7 3.2 34.7 21.5 1.51 39.8 23.0 60.0 1.7 1.4 3.2 34.7 21.5 1.51 39.8 23.0 60.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TZ H/V 036 (Part Load) with Modulating Valve or Variable Speed Pump 950 CFM Nominal (Rated) Airflow Cooling, 950 CFM Nominal (Rated) Airflow Heating WPD EWT °F 20 30 40 50 60 70 80 90 100 110 120 COOLING - EAT 80/67°F GPM PSI FT Performance capacities shown in thousands of Btuh TC SC kW HR WPD EER LWT HWG Cap GPM HEATING - EAT 70ºF PSI FT HC kW HE COP LAT LWT HWG Cap 1.7 0.1 0.2 31.1 22.0 0.98 34.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TZ H/V 036 (Full Load) with Modulating Valve or Variable Speed Pump 1150 CFM Nominal (Rated) Airflow Cooling, 1150 CFM Nominal (Rated) Airflow Heating WPD EWT °F GPM 20 30 40 50 60 70 80 90 100 110 120 Performance capacities shown in thousands of Btuh COOLING - EAT 80/67°F WPD HR EER LWT HWG Cap GPM 40.8 27.6 1.69 46.6 24.1 60.0 1.8 0.3 40.8 27.6 1.69 46.6 24.1 60.0 0.1 0.3 40.8 27.6 1.69 46.6 24.1 0.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TZ H/V 042 (Part Load) with Modulating Valve or Variable Speed Pump 1100 CFM Nominal (Rated) Airflow Cooling, 1100 CFM Nominal (Rated) Airflow Heating WPD EWT °F GPM 20 30 40 50 60 70 80 90 100 110 120 Performance capacities shown in thousands of Btuh COOLING - EAT 80/67°F WPD EER LWT HWG Cap GPM 2.6 37.6 28.3 1.26 41.9 29.8 60.0 1.2 2.5 37.6 28.3 1.26 41.9 29.8 60.0 1.2 1.1 2.5 37.6 28.3 1.26 41.9 29.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TZ H/V 042 (Full Load) with Modulating Valve or Variable Speed Pump 1300 CFM Nominal (Rated) Airflow Cooling, 1300 CFM Nominal (Rated) Airflow Heating WPD EWT °F GPM 20 30 40 50 60 70 80 90 100 110 120 Performance capacities shown in thousands of Btuh COOLING - EAT 80/67°F WPD HEATING - EAT º70F HR EER LWT HWG Cap GPM 3.4 49.4 36.1 2.09 56.6 23.6 60.0 1.7 10.5 8.4 3.6 49.4 36.1 2.09 56.6 23.6 60.0 1.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TZ H/V 048 (Part Load) with Modulating Valve or Variable Speed Pump 1250 CFM Nominal (Rated) Airflow Cooling, 1250 CFM Nominal (Rated) Airflow Heating WPD EWT °F GPM 20 30 40 50 60 70 80 90 100 110 120 Performance capacities shown in thousands of Btuh COOLING - EAT 80/67°F WPD PSI FT TC SC kW HR EER LWT HWG Cap GPM 2.3 0.7 1.6 41.2 28.3 1.50 46.3 27.5 60.0 1.5 3.1 0.7 1.7 41.2 28.3 1.50 46.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TZ H/V 048 (Full Load) with Modulating Valve or Variable Speed Pump 1500 CFM Nominal (Rated) Airflow Cooling, 1500 CFM Nominal (Rated) Airflow Heating WPD EWT °F GPM 20 30 40 50 60 70 80 90 100 110 Performance capacities shown in thousands of Btuh COOLING - EAT 80/67°F WPD PSI FT TC SC kW HR EER LWT HWG Cap GPM 3.1 1.1 2.5 54.1 36.1 2.36 62.2 23.0 60.0 2.5 4.1 1.2 2.8 54.1 36.1 2.36 62.2 23.0 60.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TZ H/V 060 (Part Load) with Modulating Valve or Variable Speed Pump 1600 CFM Nominal (Rated) Airflow Cooling, 1600 CFM Nominal (Rated) Airflow Heating WPD EWT °F GPM 20 30 40 50 60 70 80 90 100 110 120 COOLING - EAT 80/67°F Performance capacities shown in thousands of Btuh WPD HEATING - EATº70F HR EER HWG GPM LWT Cap 53.7 36.4 1.66 59.3 32.3 60.0 1.5 12.0 6.0 13.8 27.4 2.69 18.2 3.0 53.7 36.4 1.66 59.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TZ H/V 060 (Full Load) with Modulating Valve or Variable Speed Pump 1900 CFM Nominal (Rated) Airflow Cooling, 1900 CFM Nominal (Rated) Airflow Heating WPD EWT °F GPM 20 30 40 50 60 70 80 90 100 110 120 Performance capacities shown in thousands of Btuh COOLING - EAT 80/67°F WPD HR EER LWT HWG Cap GPM 1.1 72.0 47.3 2.89 81.9 24.9 60.0 2.5 14.0 7.9 0.9 2.2 72.0 47.3 2.89 81.9 24.9 60.0 2.5 7.0 1.8 5.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P Part Load Performance Data – Correction Tables Air Flow Correction Table Airflow Heating % of Rated Heating Capacity 80 85 Cooling Power Heat of Extraction Total Capacity Sensible Capacity S/T Power Heat of Rejection 0.979 1.035 0.965 0.980 0.917 0.936 0.955 0.975 0.984 1.021 0.975 0.986 0.939 0.953 0.964 0.982 90 0.990 1.011 0.984 0.992 0.961 0.969 0.975 0.988 95 0.995 1.004 0.993 0.996 0.981 0.985 0.986 0.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P Full Load Performance Data – Correction Tables Air Flow Correction Table Airflow Heating % of Rated Heating Capacity 80 85 Cooling Power Heat of Extraction Total Capacity Sensible Capacity S/T Power Heat of Rejection 0.983 1.040 0.967 0.976 0.919 0.941 0.939 0.969 0.987 1.018 0.978 0.984 0.941 0.957 0.953 0.977 90 0.991 1.004 0.988 0.990 0.962 0.972 0.968 0.986 95 0.996 0.998 0.995 0.996 0.982 0.986 0.983 0.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P High Head Variable Pump Performance High Head Variable Pump Performance Magna Geo 25-140 Pump Curve 60 50 Head (Ft.) 40 30 20 10 0 0 5 10 15 20 25 30 35 40 Flow (GPM) GPM Head (ft) 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0 14.0 15.0 16.0 17.0 18.0 19.0 20.0 21.0 22.0 23.0 24.0 25.0 44.7 45.4 46.1 46.8 47.5 47.7 47.1 46.1 45.3 43.9 42.6 41.2 39.9 38.7 37.4 36.1 34.9 33.7 32.5 31.3 30.1 28.9 27.8 26.7 25.6 24.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P Antifreeze & Water Pressure Drop Adder for Options – Correction Tables Antifreeze Correction Table Antifreeze % Antifreeze Type Water Propylene Glycol Methanol Ethanol Ethylene Glycol Cooling Heating EWT 90°F EWT 30°F WPD Corr. Fct. EWT 30°F Total Cap Sens Cap Power Htg Cap Power 0 1.000 1.000 1.000 1.000 1.000 1.000 5 0.995 0.995 1.003 0.989 N/A N/A 0.997 1.070 N/A 15 0.986 0.986 1.009 0.968 0.990 1.210 25 0.978 0.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P ECM Blower Control The ECM fan is controlled directly by the DXM2 control board that converts thermostat inputs and CFM settings to signals used by the ECM motor controller. To take full advantage of the ECM motor features, a communicating multi-stage thermostat should be used (ATC32U**). The DXM2 control maintains a selectable operating airflow [CFM] for each heat pump operating mode. For each operating mode there are maximum and minimum airflow limits.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P Blower Performance Data Model 024 030 036 042 048 060 Max ESP (in wg) Fan Motor (hp) Range Default 750 575 650 500 750 575 350 750 0.75 1/2 Maximum 850 650 800 600 850 850 850 850 0.5 0.6 0.6 0.75 0.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P Physical Data Model 024 030 036 Compressor (1 Each) 042 048 060 70 80 84 Scroll Factory Charge HFC-410A (oz) 51 48 54 ECM Fan Motor & Blower Fan Motor (hp) 1/2 1/2 1/2 3/4 3/4 1 Blower Wheel Size (dia x w) - (in) 9X7 9X7 9X8 9X8 10X10 11X10 3/4” 3/4” 3/4” 3/4" 1" 1" 0.323 0.323 0.738 0.89 0.738 0.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P TZ - Horizontal Dimensional Data Overall Cabinet Horizontal Model A Width B Length C Height 024 - 030 in cm 22.4 56.9 48.3 122.7 18.3 46.5 036 - 042 in cm 22.4 56.9 53.1 134.9 21.3 54.1 048 - 060 in cm 25.4 64.5 68.0 172.7 21.3 54.1 Water Connections 1 Horizontal Model 2 Loop In D Loop In E Loop Out F Loop Out E 3 4 5 Cond.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P TZ - Horizontal Dimensional Data Discharge Connection Duct Flange Installed (+/- 0.10 in, +/- 2.5mm) Horizontal Model Return Connection Using Return Air Opening L M Supply Height N Supply Width O P Q Return Width R Return Height S T 024 - 030 in cm 1.2 3.0 13.1 33.3 9.7 24.6 3.9 9.9 4.0 10.2 22.9 58.2 16.3 41.4 0.8 2.0 1.0 2.5 036 - 042 in cm 2.4 6.1 16.1 40.9 11.0 27.9 2.9 7.4 2.7 6.9 26.1 66.3 19.3 49.0 0.8 2.0 1.0 2.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P TZ - Vertical Upflow Dimensional Data Overall Cabinet Vertical Upflow Model Electrical Knockouts A Width B Depth C Height 024 - 030 in cm 22.4 56.9 22.4 56.9 40.5 102.9 036 - 042 in cm 22.4 56.9 25.4 64.5 46.5 118.1 048 - 060 in cm 25.4 64.5 29.1 73.9 50.5 128.3 Vertical Model 024 - 060 in cm J 1/2” K 1/2” L 3/4” Low Voltage Low Voltage Power Supply 4.0 10.2 7.0 17.8 10.0 25.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P TZ - Vertical Upflow Dimensional Data Discharge Connection Duct Flange Installed (+/- 0.10 in, +/- 2.5mm) Vertical Model Return Connection Using Return Air Opening M N O Supply Width P Supply Depth Q R S Return Depth T Return Height U 024 - 030 in cm 7.2 18.3 4.2 10.7 14.0 35.6 14.0 35.6 6.7 17.0 2.2 5.6 18.4 46.7 20.3 51.6 1.1 2.8 036 - 042 in cm 7.2 18.3 6.0 15.2 14.0 35.6 14.0 35.6 6.5 16.5 2.1 5.3 22.9 58.2 24.3 61.7 1.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P Corner Weights Corner Weights for TZ Series Horizontal Units Model 024 030 036 042 048 060 Total Left-Front* Right-Front* Left-Back* Right-Back* Lbs 208 68 56 42 42 kg 94 31 25 19 19 Lbs 208 68 56 42 42 kg 94 31 25 19 19 Lbs 233 76 63 47 47 kg 106 35 29 21 21 Lbs 244 80 66 49 49 kg 111 37 30 22 22 Lbs 299 98 81 60 60 kg 136 45 37 27 27 Lbs 314 103 85 63 63 kg 142 46 38 29 29
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P Electrical Data Units with Modulating Motorized Valve Model Voltage Code G E H F* G E H F* G E H F* G H F* G E H F* G E H F* 024 030 036 042 048 060 Voltage 208/230/60/1 265/60/1 208/230/60/3 460/60/3* 208/230/60/1 265/60/1 208/230/60/3 460/60/3* 208/230/60/1 265/60/1 208/230/60/3 460/60/3* 208/230/60/1 208/230/60/3 460/60/3* 208/230/60/1 265/60/1 208/230/60/3 460/60/3* 208/230/60/1 265/60/1 208/230/60/3 460/60/3* Min/Max Compressor Fan Motor To
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P Electrical Data Units with High Head Variable Pump Model Voltage Code G H G H G H G H G H G H 024 030 036 042 048 060 Voltage Voltage 208/230/60/1 208/230/60/3 208/230/60/1 208/230/60/3 208/230/60/1 208/230/60/3 208/230/60/1 208/230/60/3 208/230/60/1 208/230/60/3 208/230/60/1 208/230/60/3 Compressor Min/ Max 197/252 197/252 197/252 197/252 197/252 197/252 197/252 197/252 197/252 197/252 197/252 197/252 RLA LRA Qty 11.7 6.5 14.7 8.7 18.0 11.6 21.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P TZ Series Wiring Diagram Matrix Only DXM 2 diagrams, with a representative diagram of LON and MPC Options are presented in this submittal. Other diagrams can be located online at climatemaster.com using the part numbers presented below.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Wiring Diagram – Single Phase TZ Units with DXM2 Controller ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Wiring Diagram – Single Phase TZ Units with DXM2 Controller and MPC ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Wiring Diagram – Three Phase 208/230V TZ Units with DXM2 Controller ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Wiring Diagram – Three Phase 208/230V TZ Units with DXM2 Controller and LON ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Wiring Diagram – Three Phase 460V TZ Units with DXM2 Controller Note: 460V Units with ECM Motor Require A Neutral Wire. ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® 22 (TZ) Series 60Hz Engineering Specifications – Page 1 General: Furnish and install ClimateMaster Tranquility® “TZ” Water Source Heat Pumps, as indicated on the plans. Equipment shall be completely assembled, piped, and internally wired. Capacities and characteristics as listed in the schedule and the specifications that follow.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® 22 (TZ) Series 60Hz Engineering Specifications – Page 2 Cabinets shall have separate holes and knockouts for entrance of line voltage and low voltage control wiring. All factory-installed wiring passing through factory knockouts and openings shall be protected from sheet metal edges at openings by plastic ferrules.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® 22 (TZ) Series 60Hz Engineering Specifications – Page 3 Refrigerant to air heat exchangers shall utilize enhanced corrugated lanced aluminum fins and rifled copper tube construction rated to withstand 625 PSIG (4309 kPa) refrigerant working pressure.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® 22 (TZ) Series 60Hz Engineering Specifications – Page 4 • • • • • • • • • • • • • • • • • • Unit Performance Sentinel (UPS). The UPS warns when the heat pump is running inefficiently. Water coil low temperature sensing (selectable for water or antifreeze). Air coil low temperature sensing. Removable thermostat connector. Night setback control. Random start on return from night setback.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® 22 (TZ) Series 60Hz Engineering Specifications – Page 5 a. b. c. d. e. f. g. h. i. j. k. l. m. n. o. p. q. r.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® 22 (TZ) Series 60Hz Engineering Specifications – Page 6 FIELD INSTALLED OPTIONS Hose Kits: All units shall be connected with hoses. The hoses shall be 2 feet (61cm) long, braided stainless steel; fire rated hoses complete with adapters. Only fire rated hoses will be accepted. Valves: The following valves are available and will be shipped loose: a. Ball valve; bronze material, standard port full flow design, FPT connections. b.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® 22 (TZ) Series 60Hz Engineering Specifications – Page 7 sensor (AST008). Thermostat navigation shall be accomplished via five buttons (up/down/right/left/select) with menu-driven selections for ease of use and programming. d.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P Notes: ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
TZ Series 60Hz - HFC-410A Submittal Data Eng/I-P Revision History Date: Item: Action: 05/12/15 Decoder - Page 10 Changed to Rev C 12/17/14 Table - Page 30 Updated 10/15/14 Performance Data Tables Updated 09/30/14 Text Edit - Page 46 Updated 06/16/14 Page 45 Changed “rack” to “rails” 05/05/14 Page 12-23 Update table notes re. LWT 04/17/14 Page 44 Update text re.