H&V Products Tranquility 27™ (TT) Series Tranquility 20™ (TS) Series Genesis Packaged (GS) Series Residential Horizontal & Vertical Packaged Geothermal Heat Pumps Installation, Operation & Maintenance Instructions 97B0045N01 Revision: 22 Dec, 2008 Table of Contents Model Nomenclature Storage Pre-Installation Horizontal Unit Installation Field Conversion of Air Discharge Condensate Piping Installation Duct System Installation Vertical Unit Installation Water Connections Ground Loop Applications Open Loop -
Residential H&V - 60Hz R22 &R410A R e v.
Residential H&V - 60Hz R22 &R410A R e v.
Residential H&V - 60Hz R22 &R410A R e v. : 2 2 D e c , 2 0 0 8 General Information Inspection Upon receipt of the equipment, carefully check the shipment against the bill of lading. Make sure all units have been received. Inspect the packaging of each unit, and inspect each unit for damage. Insure that the carrier makes proper notation of any shortages or damage on all copies of the freight bill and completes a common carrier inspection report.
Residential H&V - 60Hz R22 &R410A R e v. : 2 2 D e c , 2 0 0 8 Horizontal Installation NOTICE! Failure to remove shipping brackets from springmounted compressors will cause excessive noise, and could cause component failure due to added vibration. Horizontal Unit Location Units are not designed for outdoor installation. Locate the unit in an INDOOR area that allows enough space for service personnel to perform typical maintenance or repairs without removing unit from the ceiling.
Residential H&V - 60Hz R22 &R410A R e v.
Residential H&V - 60Hz R22 &R410A R e v. : 2 2 D e c , 2 0 0 8 Field Conversion of Air Discharge Overview Horizontal units can be field converted between side (straight) and back (end) discharge using the instructions below. Figure 4: Left Return Side to Back Remove Screws Water Connection End Return Air Note: It is not possible to field convert return air between left or right return models due to the necessity of refrigeration copper piping changes.
Residential H&V - 60Hz R22 &R410A R e v. : 2 2 D e c , 2 0 0 8 Horizontal Installation Condensate Piping – Horizontal Units Pitch the unit toward the drain as shown in Figure 2 to improve the condensate drainage. On small units (less than 2.5 tons/8.8 kW), insure that unit pitch does not cause condensate leaks inside the cabinet. Install condensate trap at each unit with the top of the trap positioned below the unit condensate drain connection as shown in Figure 6.
Residential H&V - 60Hz R22 &R410A R e v. : 2 2 D e c , 2 0 0 8 Vertical Installation Vertical Unit Location Units are not designed for outdoor installation. Locate the unit in an INDOOR area that allows enough space for service personnel to perform typical maintenance or repairs without removing unit from the mechanical room/closet. Vertical units are typically installed in a mechanical room or closet.
Residential H&V - 60Hz R22 &R410A R e v. : 2 2 D e c , 2 0 0 8 Vertical Installation Sound Attenuation for Vertical Units Sound attenuation is achieved by enclosing the unit within a small mechanical room or a closet. Additional measures for sound control include the following: 1. Mount the unit so that the return air inlet is 90° to the return air grille. Refer to Figure 9. Install a sound baffle as illustrated to reduce line-of sight sound transmitted through return air grilles. 2.
Residential H&V - 60Hz R22 &R410A R e v. : 2 2 D e c , 2 0 0 8 Water Connection Installation External Flow Controller Mounting The Flow Controller can be mounted beside the unit as shown in Figure 12. Review the Flow Controller installation manual for more details. Water Connections-Residential (Distributor) Models Residential models utilize swivel piping fittings for water connections that are rated for 450 psi (3101 kPa) operating pressure.
Residential H&V - 60Hz R22 &R410A R e v. : 2 2 D e c , 2 0 0 8 Ground-Loop Heat Pump Applications from the system, the level will drop only 1-2 inches (2.5 - 5 cm) in a 10” (25 cm) diameter PVC flush tank (about a half gallon [2.3 liters]), since liquids are incompressible. If the level drops more than this, flushing should continue since air is still being compressed in the loop fluid. Perform the “dead head” procedure a number of times.
Residential H&V - 60Hz R22 &R410A R e v. : 2 2 D e c , 2 0 0 8 Ground-Loop Heat Pump Applications Figure 12: Typical Ground-Loop Application Flow Controller Unit Power Disconnect Insulated Hose Kit Thermostat Wiring P/T Plugs Rev.: 06/10/05D ASP30 Air Pad or Extruded polystyrene insulation board Do not install bricks or blocks under air pad. GROUND-WATER HEAT PUMP APPLICATIONS Open Loop - Ground Water Systems Typical open loop piping is shown in Figure 13.
Residential H&V - 60Hz R22 &R410A R e v. : 2 2 D e c , 2 0 0 8 Ground-Water Heat Pump Applications applications should be considered for the inherent energy savings and smaller expansion tank requirements. Water Control Valve Note the placement of the water control valve in figure 13. Always maintain water pressure in the heat exchanger by placing the water control valve(s) on the discharge line to prevent mineral precipitation during the off-cycle.
Residential H&V - 60Hz R22 &R410A R e v.
Residential H&V - 60Hz R22 &R410A R e v. : 2 2 D e c , 2 0 0 8 Hot Water Generator The HWG (Hot Water Generator) or desuperheater option provides considerable operating cost savings by utilizing excess heat energy from the heat pump to help satisfy domestic hot water requirements. The HWG is active throughout the year, providing virtually free hot water when the heat pump operates in the cooling mode or hot water at the COP of the heat pump during operation in the heating mode.
Residential H&V - 60Hz R22 &R410A R e v. : 2 2 D e c , 2 0 0 8 Hot Water Generator Installation The HWG high limit temperature switch is set at 125°F [52°C] and is located on the HWG heat exchanger “Water In” line. If the HWG is connected incorrectly or if circulation is reversed, the aquastat will sense leaving water temperature and prevent HWG operation.
Residential H&V - 60Hz R22 &R410A R e v. : 2 2 D e c , 2 0 0 8 Electrical - Line Voltage WARNING! CAUTION! WARNING! To avoid possible injury or death due to electrical shock, open the power supply disconnect switch and secure it in an open position during installation. CAUTION! Use only copper conductors for field installed electrical wiring. Unit terminals are not designed to accept other types of conductors.
Residential H&V - 60Hz R22 &R410A R e v. : 2 2 D e c , 2 0 0 8 Electrical - Line Voltage Table 4c: Genesis Packaged (GS) Series Electrical Data RLA LRA Qty HWG Pump FLA 015 6.1 29.0 1 0.4 4.0 1.0 11.5 13.0 15 12 56 (17.2) 018 7.7 38.0 1 0.4 4.0 1.0 13.1 15.0 20 12 77 (23.6) 100 (30.7) Model Compressor Ext Loop Pump FLA Fan Motor FLA Total Unit FLA Min Circuit Amps Max Fuse/ HACR Min AWG Max Ft (m) PSC Electrical Data 024 10.3 56.0 1 0.4 4.0 1.1 15.8 18.
Residential H&V - 60Hz R22 &R410A R e v. : 2 2 D e c , 2 0 0 8 Electrical - Power Wiring Power Connection Line voltage connection is made by connecting the incoming line voltage wires to the “L” side of the contactor as shown in Figures 17 and 18. Consult Tables 4a through 4c for correct fuse size. Figure 17: GS Single Phase Line Voltage Field Wiring Capacitor Contactor -CC 208 Volt Operation All residential 208-230 Volt units are factory wired for 230 Volt operation.
Residential H&V - 60Hz R22 &R410A R e v. : 2 2 D e c , 2 0 0 8 Electrical - Low Voltage Wiring Thermostat Connections The thermostat should be wired directly to the CXM board (units with PSC fan). Units with optional ECM motor include factory wiring from the CXM board to the ECM interface board. Thermostat wiring for these units should be connected to the ECM interface board. Figure 20 shows wiring for 50YC units; Figure 19 should be used for TT/TS units with PSC or optional ECM motor.
Residential H&V - 60Hz R22 &R410A R e v. : 2 2 D e c , 2 0 0 8 Electrical - Low Voltage Wiring Accessory Connections A terminal paralleling the compressor contactor coil has been provided on the CXM control. Terminal “A” is designed to control accessory devices, such as water valves. Note: This terminal should be used only with 24 Volt signals and not line voltage. Terminal “A” is energized with the compressor contactor. See Figure 23 or the specific unit wiring diagram for details.
Residential H&V - 60Hz R22 &R410A R e v. : 2 2 D e c , 2 0 0 8 Electrical - Thermostat Wiring Figure 26: Units With Optional ECM Fan. CAUTION! Connection to ECM Control CAUTION! Many units are installed with a factory or field supplied manual or electric shut-off valve. DAMAGE WILL OCCUR if shut-off valve is closed during unit operation.
Residential H&V - 60Hz R22 &R410A R e v. : 2 2 D e c , 2 0 0 8 ECM Blower Control The ECM fan is controlled by an interface board that converts thermostat inputs and field selectable CFM settings to signals used by the ECM motor controller. Units manufactured before July 2005 have version I (P/N 69243707). Units manufactured after July 2005 have version II (P/N 17B0019N01). Fan speeds are selected with jumpers for version I or via a nine position DIP switch for version II.
Residential H&V - 60Hz R22 &R410A R e v. : 2 2 D e c , 2 0 0 8 ECM Blower Control Table 5: ECM Board Tap Settings Cooling settings: TT, TS, GS units* Version I Version II 69243707 17B0019N01 Tap HP CFM DIP Switch Setting Jumper SW1 SW2 1 1 ON ON 2 2 ON OFF 3 3 OFF ON 4 4 OFF OFF *GS units use the same settings for both cooling (normal) CFM and heating CFM.
Residential H&V - 60Hz R22 &R410A R e v. : 2 2 D e c , 2 0 0 8 Tranquility 27™ (TT) Series ECM Blower Performance Data Residential Units Only Airflow in CFM with wet coil and clean air filter Model 026 038 049 064 072 Max ESP (in. wg) Fan Motor (hp) Tap Setting Cooling Mode Dehumid Mode Heating Mode Stg 1 Stg 2 Fan Stg 1 Stg 2 Fan Stg 1 Stg 2 0.50 1/2 4 810 950 475 630 740 475 920 0.50 1/2 3 725 850 425 560 660 425 825 0.50 1/2 2 620 730 370 490 570 370 0.
Residential H&V - 60Hz R22 &R410A R e v. : 2 2 D e c , 2 0 0 8 Tranquility 20™ (TS) Series PSC Blower Performance Data Airflow in CFM with wet coil and clean air filter Model 018 024 030 036 042 048 060 070 Airflow (cfm) at External Static Pressure (in. wg) Fan Speed Rated Airflow Min CFM 0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.60 0.
Residential H&V - 60Hz R22 &R410A R e v. : 2 2 D e c , 2 0 0 8 Tranquility 20™ (TS) Series ECM Blower Performance Data Residential Units Only Airflow in CFM with wet coil and clean air filter Model 018 024 030 036 042 048 060 070 Max ESP (in. wg) 0.50 0.50 0.50 0.50 0.50 0.75 0.75 0.
Residential H&V - 60Hz R22 &R410A R e v. : 2 2 D e c , 2 0 0 8 Genesis (GS) Series ECM Blower Performance Data Residential Units Only Airflow in CFM with wet coil and clean air filter Model 015 018 024 030 036 042 048 060 070 Max ESP (in. wg) 0.50 0.50 0.50 0.50 0.50 0.50 0.75 0.75 0.
Residential H&V - 60Hz R22 &R410A R e v. : 2 2 D e c , 2 0 0 8 Genesis (GS) Series PSC Blower Performance Data Model 015 018 024 030 036 042 048 060 070 Airflow (cfm) at External Static Pressure (in. wg) Fan Speed Rated Airflow MIN CFM 0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.
Residential H&V - 60Hz R22 &R410A R e v. : 2 2 D e c , 2 0 0 8 CXM Controls CXM Control For detailed control information, see CXM Application, Operation and Maintenance (AOM) manual (part #97B0003N12). DDC operation. If set to “DDC Output at EH2,” the EH2 terminal will continuously output the last fault code of the controller. If set to “EH2 normal,” EH2 will operate as standard electric heat output.
Residential H&V - 60Hz R22 &R410A R e v. : 2 2 D e c , 2 0 0 8 CXM Controls Safety Features – CXM Control The safety features below are provided to protect the compressor, heat exchangers, wiring and other components from damage caused by operation outside of design conditions. Anti-short cycle protection: The control features a 5 minute anti-short cycle protection for the compressor. Note: The 5 minute anti-short cycle also occurs at power up.
Residential H&V - 60Hz R22 &R410A R e v. : 2 2 D e c , 2 0 0 8 CXM Controls CXM Control Start-up Operation The control will not operate until all inputs and safety controls are checked for normal conditions. The compressor will have a 5 minute anti-short cycle delay at power-up. The first time after power-up that there is a call for compressor, the compressor will follow a 5 to 80 second random start delay. After the random start delay and anti-short cycle delay, the compressor relay will be energized.
Residential H&V - 60Hz R22 &R410A R e v. : 2 2 D e c , 2 0 0 8 CXM Controls Table 7: Nominal resistance at various temperatures ϒ ϒ ϒ CXM Thermostat Details Thermostat Compatibility - Most all heat pump thermostats can be used with the CXM control. However Heat/Cool stats are NOT compatible with the CXM. ϒ Anticipation Leakage Current - Maximum leakage current for "Y" is 50 mA and for "W" is 20mA. Triacs can be used if leakage current is less than above.
Residential H&V - 60Hz R22 &R410A R e v. : 2 2 D e c , 2 0 0 8 Unit Starting And Operating Conditions Determination of operating limits is dependent primarily upon three factors: 1) return air temperature. 2) water temperature, and 3) ambient temperature. When any one of these factors is at minimum or maximum levels, the other two factors should be at normal levels to insure proper unit operation. Consult product catalog for operating temperature limits.
Residential H&V - 60Hz R22 &R410A R e v. : 2 2 D e c , 2 0 0 8 Unit Starting and Operating Conditions Unit and System Checkout BEFORE POWERING SYSTEM, please check the following: UNIT CHECKOUT Balancing/shutoff valves: Insure that all isolation valves are open and water control valves are wired. Line voltage and wiring: Verify that voltage is within an acceptable range for the unit and wiring and fuses/ breakers are properly sized. Verify that low voltage wiring is complete.
Residential H&V - 60Hz R22 &R410A R e v. : 2 2 D e c , 2 0 0 8 Unit Start-Up Procedure c. Verify that the compressor is on and that the water flow rate is correct by measuring pressure drop through the heat exchanger using the P/T plugs and comparing to Tables 9a through 9c. d. Check the elevation and cleanliness of the condensate lines. Dripping may be a sign of a blocked line. Check that the condensate trap is filled to provide a water seal. e. Refer to Table 10.
Residential H&V - 60Hz R22 &R410A R e v. : 2 2 D e c , 2 0 0 8 Unit Operating Conditions Table 9a: TT Coax Water Pressure Drop Model GPM 026 038 Table 9b: TS Coax Water Pressure Drop Pressure Drop (psi) 30°F 50°F 70°F 90°F 4.0 6.0 7.0 8.0 1.5 3.1 4.1 5.1 1.3 2.6 3.4 4.3 1.1 2.3 3.0 3.8 1.0 2.1 2.7 3.4 4.0 6.0 8.0 9.0 1.2 2.6 4.5 5.7 1.0 2.5 4.2 5.2 0.8 2.3 4.0 4.8 0.6 2.1 3.7 4.4 5.5 8.3 11.0 12.0 1.1 2.2 3.9 4.5 0.9 2.1 3.6 4.2 0.8 2.0 3.2 3.8 0.7 1.8 3.1 3.5 064 7.0 10.5 14.0 15.
Residential H&V - 60Hz R22 &R410A R e v. : 2 2 D e c , 2 0 0 8 Unit Operating Conditions Table 11: TT Series Typical Unit Operating Pressures and Temperatures 026 Full Load Cooling - without HWG active Entering Water Temp °F Water Flow GPM/ton Suction Pressure PSIG Discharge Pressure PSIG 30 1.5 2.25 3 118-128 118-128 118-128 50 1.5 2.
Residential H&V - 60Hz R22 &R410A R e v.
Residential H&V - 60Hz R22 &R410A R e v.
Residential H&V - 60Hz R22 &R410A R e v. : 2 2 D e c , 2 0 0 8 Unit Operating Conditions Table 12: TS Series Typical Unit Operating Pressures and Temperatures: Continued 042 Full Load Cooling - without HWG active Entering Water Temp °F Water Flow GPM/ton Suction Pressure PSIG Discharge Pressure PSIG Superheat Subcooling Water Temp Rise °F Air Temp Drop °F DB Suction Pressure PSIG Discharge Pressure PSIG Superheat Subcooling Water Temp Drop °F Air Temp Rise °F DB 30 1.5 2.
Residential H&V - 60Hz R22 &R410A R e v.
Residential H&V - 60Hz R22 &R410A R e v. : 2 2 D e c , 2 0 0 8 Preventive Maintenance Water Coil Maintenance (Direct ground water applications only) - If the system is installed in an area with a known high mineral content (125 P.P.M. or greater) in the water, it is best to establish a periodic maintenance schedule with the owner so the coil can be checked regularly. Consult the well water applications section of this manual for a more detailed water coil material selection.
Residential H&V - 60Hz R22 &R410A R e v. : 2 2 D e c , 2 0 0 8 Troubleshooting General If operational difficulties are encountered, perform the preliminary checks below before referring to the troubleshooting charts. • Verify that the unit is receiving electrical supply power. • Make sure the fuses in the fused disconnect switches are intact. After completing the preliminary checks described above, inspect for other obvious problems such as leaking connections, broken or disconnected wires, etc.
Residential H&V - 60Hz R22 &R410A R e v. : 2 2 D e c , 2 0 0 8 CXM Process Flow Chart WARNING! WARNING! HAZARDOUS VOLTAGE! DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS BEFORE SERVICING. Failure to disconnect power before servicing can cause severe personal injury or death.
Residential H&V - 60Hz R22 &R410A R e v. : 2 2 D e c , 2 0 0 8 Functional Troubleshooting Only Compressor Runs X X Thermostat wiring Check G wiring at heat pump. Jumper G and R for fan operation. X X Fan motor relay Jumper G and R for fan operation. Check for Line voltage across BR contacts.
Residential H&V - 60Hz R22 &R410A R e v.
Residential H&V - 60Hz R22 &R410A R e v.
Residential H&V - 60Hz R22 &R410A R e v. : 2 2 D e c , 2 0 0 8 Revision History Page # 22 Dec, 08 8 Condensate Piping Information Changed 05 June, 08 All Reformatted Document Size 21 Aug, 07 All Updated with Model 072 Information 01 Oct, 06 All First Published Description R AI BR I HE AT P U M P S A TO NE WATER TO IFIED TO ARI A RT S C CE NG WITH LYI MP O IR MANUFACT UR ER Date IS ST AND 3 ARD 1 -1 R O 25 6 ISO 9001:2000 Certified Quality: First & Always 7300 S.W.