Specifications

ClimateMaster works continually to improve its products. As a result, the design and speci cations of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer
Service Department at 1-405-745-6000 for speci c information on the current design and speci cations. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties,
but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.
Page ______ of ______Rev.: 20 May, 2009BLC291 - 8
CCE Series 60Hz - R22 Submittal Data Eng/I-P
Geothermal Heat Pump Systems
Performance Data
ARI/ASHRAE/ISO 13256-1
Model
Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump
Cooling 86°F Heating 68°F Cooling 59°F Heating 50°F Cooling 77°F Heating 32°F
Capac-
ity
Btuh
EER
Btuh/W
Capac-
ity
Btuh
COP
Capac-
ity
Btuh
EER
Btuh/W
Capac-
ity
Btuh
COP
Capac-
ity
Btuh
EER
Btuh/W
Capac-
ity
Btuh
COP
CCE07
7,800 12.1 10,400 4.9 8,900 19.5 8,400 4.3 8,000 14.0 6,500 3.6
CCE09
9,300 12.0 12,000 4.4 10,300 18.1 9,700 3.8 10,000 14.0 7,800 3.4
CCE12
12,300 11.6 15,000 4.4 13,700 17.8 12,400 3.8 12,800 13.4 9,800 3.3
CCE15
13,800 11.8 17,300 4.4 15,200 17.3 14,000 3.8 14,100 13.5 11,000 3.3
CCE19
16,000 12.0 19,300 4.2 17,800 17.3 16,000 3.7 16,400 13.4 12,500 3.1
Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature
Heating capacities based upon 68°F DB, 59°F WB entering air temperature
All air ow is rated on high speed
All ratings based upon operation at lower voltage of dual voltage rated models
ASHRAE/ARI/ISO 13256-1. English (IP) Units
Model
Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump
Cooling 30°C Heating 20°C Cooling 15°C Heating 10°C Cooling 25°C Heating 0°C
Capac-
ity
Watts
EER
W/W
Capac-
ity
Watts
COP
Capac-
ity
Watts
EER
W/W
Capac-
ity
Watts
COP
Capac-
ity
Watts
EER
W/W
Capac-
ity
Watts
COP
CCE07
2,286 3.5 3,048 4.9 2,608 5.7 2,462 4.3 2,345 4.1 1,905 3.6
CCE09
2,726 3.5 3,517 4.4 3,019 5.3 2,843 3.8 2,931 4.1 2,286 3.4
CCE12
3,605 3.4 4,396 4.4 4,015 5.2 3,634 3.8 3,751 3.9 2,872 3.3
CCE15
4,045 3.5 5,070 4.4 4,455 5.1 4,103 3.8 4,132 4.0 3,224 3.3
CCE19
4,689 3.5 5,657 4.2 5,217 5.1 4,689 3.7 4,807 3.9 3,664 3.1
Cooling capacities based upon 27°C DB, 19°C WB entering air temperature
Heating capacities based upon 20°C DB, 15°C WB entering air temperature
All air ow is rated on high speed
All ratings based upon operation at lower voltage of dual voltage rated models
ASHRAE/ARI/ISO 13256-1. Metric (SI) Units