Specifications

ClimateMaster works continually to improve its products. As a result, the design and speci cations of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer
Service Department at 1-405-745-6000 for speci c information on the current design and speci cations. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties,
but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.
Page ______ of ______Rev.: 20 May, 2009BLC291 - 5
CCE Series 60Hz - R22 Submittal Data Eng/I-P
Geothermal Heat Pump Systems
Air Flow Water Flow Ext Static Pressure Water Pressure Drop
Airflow (L/s) = CFM x 0.472 Water Flow (L/s) = gpm x 0.0631 ESP (Pa) = ESP (in of wg) x 249 PD (kPa) = PD (ft of hd) x 2.99
Reference Calculations
BTUH = BTU( British Thermal Unit) per hour
CFM = air ow, cubic feet/minute
COP = coef cient of performance = BTUH output/BTUH input
DB = dry bulb temperature (°F)
EAT = entering air temperature, Fahrenheit (dry bulb/wet bulb)
EER = energy ef ciency ratio = BTUH output/Watt input
EPT = external pipe thread
ESP = external static pressure (inches w.g.)
EWT = entering water temperature
GPM = water ow in U.S. gallons/minute
HE = total heat of extraction, BTUH
HC = air heating capacity, BTUH
HR = total heat of rejection, BTUH
HWC = hot water generator (desuperheater) capacity, Mbtuh
IPT = internal pipe thread
KW = total power unit input, kilowatts
LAT = leaving air temperature, °F
LC = latent cooling capacity, BTUH
LWT = leaving water temperature, °F
MBTUH = 1000 BTU per hour
S/T = sensible to total cooling ratio
SC = sensible cooling capacity, BTUH
TC = total cooling capacity, BTUH
WB = wet bulb temperature (°F)
WPD = waterside pressure drop (psi & ft. of hd.)
Conversion Table - to convert inch-pound (English) to SI (Metric)
Legend and Glossary of Abbreviations
LWT = EWT -
HE
GPM x 500
LAT = EAT +
HC
CFM x1.08
LWT = EWT +
HR
GPM x 500
LAT (DB) = EAT (DB) -
SC
CFM x1.08
LC = TC - SC
S/T =
SC
TC
Heating
Cooling
Selection Procedure