Specifications
ClimateMaster works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer
Service Department at 1-405-745-6000 for specifi c information on the current design and specifi cations. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties,
but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.
Page ______ of ______Rev.: 20 May, 2009BLC291 - 38
CCE Series 60Hz - R22 Submittal Data Eng/I-P
Geothermal Heat Pump Systems
Option: Extended 4-year control board warranty covers the CXM/DXM control board for a total of 5 years.
FIELD INSTALLED OPTIONS
Hose Kits:
Hoses shall be 1 foot (31cm) long, braided stainless steel; fi re rated hoses complete with adapters. Only fi re rated hoses will be
accepted. Note: Threaded connection (IPT) piping option must be ordered for hose kit connections.
Option: 2 foot (61cm) hose lengths instead of standard 1 foot (31cm) length.
Valves:
The following valves are available and will be shipped loose:
a. Ball valve; bronze material, standard port full fl ow design, IPT connections.
b. Ball valve with memory stop and PT Port; standard port full fl ow design, IPT connections.
c. “Y” strainer with cap; bronze material, IPT connections.
d. “Y” strainer with blowdown valve; bronze material, IPT connections.
e. Motorized water valve; slow acting, 24v, IPT connections.
Hose Kit Assemblies:
The following assemblies ship with the valves already assembled to the hose described:
a. Supply and return hoses having ball valve with PT port.
b. Supply hose having ball valve with PT port; return hose having automatic fl ow regulator valve with PT ports, and ball valve.
c. Supply hose having “Y” strainer with blowdown valve, and ball valve with PT port; return hose having automatic fl ow
regulator with PT ports, and ball valve.
Thermostats:
The thermostat shall be a ClimateMaster mechanical or electronic type thermostat as selected below with the described features
(Note: “Remote mounted thermostat” control option must be selected for the console unit):
a. Single Stage Standard Manual Changeover (ATM11C11)
Thermostat shall be a single-stage, horizontal mount, manual changeover with HEAT-OFF-COOL system switch and fan
ON-AUTO switch. Thermostat shall have a mechanical temperature indicator and set point indication. Thermostat shall only
require 4 wires for connection. Mercury bulb thermostats are not acceptable.
b. Single Stage Digital Auto or Manual Changeover (ATA11U01)
Thermostat shall be a single-stage, digital, auto or manual changeover with HEAT-OFF-COOL-AUTO system switch and fan
ON-AUTO switch. Thermostat shall have an LCD display with temperature and set-point(s) in ºF or ºC. The Thermostat shall
provide permanent memory of set-point(s) without batteries. A fault LED shall be provided to display specifi c fault condition.
Thermostat shall provide temperature display offset for custom applications.
c. Single Stage Digital Automatic Changeover with Two-Speed Fan Control (ATA11C04) – Recommended for Console Remote-
Mount Thermostat (DXM required)
Thermostat shall be a single-stage, digital, auto or manual changeover with HEAT-OFF-COOL-AUTO system switch, fan ON-
AUTO switch, and fan LO-HI switch. Thermostat shall have an LCD display with temperature and set-point(s) in ºF or ºC. A
fault LED shall be provided to display specifi c fault condition. Thermostat shall come standard with an on-board temperature
sensor, but may be operated with a remote sensor if desired via jumper confi guration and remote sensor, AST009.
d. Multistage Digital Automatic Changeover (ATA22U01)
Thermostat shall be multi-stage (2H/2C), manual or automatic changeover with HEAT-OFF-COOL-AUTO system settings and
fan ON-AUTO settings. Thermostat shall have an LCD display with temperature, set-point(s), mode, and status indication.
The temperature indication shall be selectable for ºF or ºC. The thermostat shall provide permanent memory of set-point(s)
without batteries. A fault LED shall be provided to indicate specifi c fault condition(s). Thermostat shall provide temperature
display offset for custom applications. Thermostat shall allow unit to provide better dehumidifi cation with optional DXM
controller by automatically using lower fan speed on stage 1 cooling (higher latent cooling) as main cooling mode, and
automatically shifting to high speed fan on stage 2 cooling.
e. Single Stage Manual Changeover Programmable 5/2 Day (ATP11N01)
Thermostat shall be 5 day/2 day programmable (with up to 4 set points per day), single stage (1H/1C), manual changeover
with HEAT-OFF-COOL system settings and fan ON-AUTO settings. Thermostat shall have an LCD display with temperature,
set-point(s), mode, and status indication. The temperature indication shall be selectable for ºF or ºC. The thermostat shall
provide permanent memory of set-point(s) without batteries. Thermostat shall provide convenient override feature to
temporarily change set point.
f. Multistage Automatic or Manual Changeover Programmable 5/2 Day (ATP21U01)
Console (CCE) Series 60Hz
Engineering Specifi cations Rev.: 05/20/09 Page 6