Specifications
ClimateMaster works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer
Service Department at 1-405-745-6000 for specifi c information on the current design and specifi cations. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties,
but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.
Page ______ of ______Rev.: 20 May, 2009BLC291 - 16
CCE Series 60Hz - R22 Submittal Data Eng/I-P
Geothermal Heat Pump Systems
Blower Performance &
Electrical Data
Blower Performance
Electrical Data
Model
Voltage
Code
Voltage
Min/Max
Voltage
Compressor
Fan
Motor
FLA
Total
Unit
FLA
Min
Circuit
Amps
Max
Fuse/
HACR
QTY RLA LRA
CCE07
A 115/60/1 104-126 1 7.1 46.5 0.50 7.6 9.3 15
CCE07
G 208-230/60/1 197-254 1 3.7 19.0 0.33 4.0 5.0 15
CCE07
E 265/60/1 239-292 1 2.8 16.0 0.35 3.1 3.8 15
CCE09
A 115/60/1 104-126 1 9.0 46.5 1.30 10.3 12.5 20
CCE09
G 208-230/60/1 197-254 1 4.7 23.0 0.50 5.2 6.3 15
CCE09
E 265/60/1 239-292 1 3.8 16.0 0.50 4.3 5.3 15
CCE12
A 115/60/1 104-126 1 10.6 63.0 1.30 11.9 14.6 25
CCE12
G 208-230/60/1 197-254 1 6.1 29.0 0.50 6.6 8.1 15
CCE12
E 265/60/1 239-292 1 4.8 21.6 0.50 5.3 6.5 15
CCE15
G 208-230/60/1 197-254 1 7.0 33.2 1.10 8.1 9.8 15
CCE15
E 265/60/1 239-292 1 5.4 29.0 1.00 6.4 7.8 15
CCE19
G 208-230/60/1 197-254 1 7.7 38.0 1.10 8.8 10.7 15
CCE19
E 265/60/1 239-292 1 5.8 29.0 1.00 6.8 8.2 15
Model
Rated
CFM
SCFM
Low
Speed
High
Speed
CCE07
240 190 240
CCE09
300 240 300
CCE12
350 300 350
CCE15
400 340 400
CCE19
460 400 460
Fan speed is user selectable
All airfl ow is rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units
All units ARI/ISO/ASHRAE 13256-1 rated on high fan speed
All units are designed and rated for zero external static pressure (non-ducted) application