Specifications
ClimateMaster works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer
Service Department at 1-405-745-6000 for specifi c information on the current design and specifi cations. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties,
but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.
Page ______ of ______Rev.: 20 May, 2009BLC291 - 15
CCE Series 60Hz - R22 Submittal Data Eng/I-P
Geothermal Heat Pump Systems
Performance Data
Correction Tables
Air Flow Correction Table
Entering Air Correction Table
Airfl ow Cooling Heating
% of
Rated
Total
Capacity
Sensible
Capacity
Power
Heat of
Rejection
Heating
Capacity
Power
Heat of
Extraction
75%
0.951 0.860 0.963 0.952 0.990 1.054 0.966
81%
0.964 0.894 0.973 0.965 0.993 1.035 0.977
88%
0.979 0.936 0.984 0.979 0.996 1.019 0.987
94%
0.990 0.969 0.992 0.990 0.998 1.008 0.994
100%
1.000 1.000 1.000 1.000 1.000 1.000 1.000
106%
1.010 1.033 1.008 1.010 1.002 0.994 1.005
113%
1.019 1.069 1.016 1.019 1.003 0.988 1.011
Cooling
Entering
Air WB°F
Total
Capacity
Sensible Cooling Capacity Multiplier -
Entering DB °F
Power
Heat of
Rejection
70 75 80 80.6 85 90 95
60 0.893 0.889 1.087 * ****0.964 0.902
65 0.964 0.692 0.884 1.085 1.108 * * * 0.988 0.967
66.2 0.983 0.645 0.838 1.036 1.059 1.231 * * 0.995 0.985
67 1.000 0.613 0.806 1.000 1.027 1.199 * * 1.000 1.000
70 1.049 * 0.683 0.879 0.902 1.077 1.274 1.415 1.016 1.046
75 1.118 * * 0.676 0.698 0.866 1.068 1.266 1.037 1.106
* = Sensible capacity equals total capacity
ARI/ISO/ASHRAE 13256-1 uses entering air conditions of Cooling - 80.6°F DB/66.2°F WB, 1
and Heating - 68°F DB/59°F WB entering air temperature
Heating
Entering
Air DB°F
Heating
Capacity
Power
Heat of
Extraction
60 1.011 0.989 1.007
65 1.004 0.994 1.004
68 1.002 0.997 1.002
70 1.000 1.000 1.000
75 0.996 1.007 0.995
80 0.991 1.018 0.990
Antifreeze Type
Antifreeze
%
Cooling Heating
WPD
Corr. Fct.
EWT 30°F
EWT 90°F EWT 30°F
Total Cap Sens Cap Power Htg Cap Power
Water
0 1.000 1.000 1.000 1.000
Propylene Glycol
5 0.995 0.995 1.003 0.989 0.997 1.070
15 0.986 0.986 1.009 0.968 0.990 1.210
25 0.978 0.978 1.014 0.947 0.983 1.360
Methanol
5 0.997 0.997 1.002 0.989 0.997 1.070
15 0.990 0.990 1.007 0.968 0.990 1.160
25 0.982 0.982 1.012 0.949 0.984 1.220
Ethanol
5 0.998 0.998 1.002 0.981 0.994 1.140
15 0.994 0.994 1.005 0.944 0.983 1.300
25 0.986 0.986 1.009 0.917 0.974 1.360
Ethylene Glycol
5 0.998 0.998 1.002 0.993 0.998 1.040
15 0.994 0.994 1.004 0.980 0.994 1.120
25 0.988 0.988 1.008 0.966 0.990 1.200
Antifreeze Correction Table