Unit Commissioning and Operating Conditions
Table 9: Water Temperature Change Through
Heat Exchanger
Environment – This unit is designed for indoor
installation only. Do not install in an area subject to
freezing or where humidity levels can cause cabinet
condensation.
Power Supply – A voltage variation of +/- 10% of
nameplate utilization voltage is acceptable.
Operation and performance is primarily dependent
upon return air temperature, airfl ow, water temperature,
water fl ow rate and ambient air temperature. This water
to air heat pump is capable of operating over a wide
temperature range and with fl ow rates of between 1.5
GPM (.1 l/s) and 3 GPM (.19 l/s) per ton, however usually
no more than one of these factors may be at a minimum
or maximum level at a time.
BUILDING COMMISSIONING
ALL CCE MODELS ALL TRC MODELS
Cooling °F [°C] Heating °F [°C] Cooling °F [°C] Heating °F [°C]
AMBIENT MIN - MAX DB
45-110 [7-43] 40-85 [4.5-29] 45-110 [7-43] 40-85 [4.5-29]
RETURN AIR MIN DB/WB
60/45 [16/7] 40 [4.5] 60/45 [16/7] 40 [4.5]
RETURN AIR MAX DB/WB
110/83 [43/28] 80 [27] 110/83 [43/28] 80 [27]
STANDARD UNIT ENTERING
WATER MIN* - MAX
40-110 [4.5-43] 60-90 [16-43] 40-120 [4.5-49] 60-90 [16-43]
EXTENDED RANGE UNIT**
ENTERING WATER MIN* - MAX
30-110 [-1-43] 20-90 [-6.7-32] 30-120 [-1-49] 20-90 [-6.7-32]
*- Requires optional insulation package when operating below the dew point
**- Requires antifreeze, optional insulation package and jumper clipped.
UNIT OPERATING LIMITS
All CCE Models All TRC Models
Cooling °F [°C] Heating °F [°C] Cooling °F [°C] Heating °F [°C]
AMBIENT MIN - MAX DB
50-100 [10-38] 50-85 [10-29] 50-100 [10-38] 50-85 [10-29]
RETURN AIR MIN DB/WB
65/60 [18/15.5] 50 [10] 65/60 [18/15.5] 50 [10]
RETURN AIR MAX DB/WB
95/75 [35/24] 80 [27] 95/75 [35/24] 80 [27]
STANDARD UNIT ENTERING
WATER MIN* - MAX
50-110 [10-43] 60-90 [16-43] 50-120 [10-49] 60-90 [16-43]
EXTENDED RANGE UNIT**
ENTERING WATER MIN* - MAX
30-110 [-1-43] 20-90 [-6.7-32] 30-120 [-1-49] 20-90 [-6.7-32]
*- Requires optional insulation package when operating below the dew point
**- Requires antifreeze, optional insulation package and jumper clipped.
Table 8: Building Commissioning
Table 8A: Unit Operating Limits
The commissioning table indicates air and water
temperatures which are suitable for initial unit
commissioning in an environment where the fl ow rate
and water temperature is not yet stable and to avoid
nuisance shut down of the units freeze and refrigerant
pressure safeties.
The operating table indicates the maximum and
minimum ranges of the unit.
For more specifi c unit performance reference the
product catalog, the submittal data sheets or contact
your supplier for assistance.