Specifications
24
ClimateMaster Water-Source Heat Pumps
Console (CCE) Series
0.5 to 1.5 Ton Console Units
Performance Data CCE-19B
EWT
°F
GPM
WPD* Cooling - EAT 80/67°F Heating - EAT 70°F
PSI FT TC SC
Sens/Tot
Ratio
kW HR EER HC kW HE LAT COP
20
4.8 7.9 18.2
Operation Not Recommended
11.2 1.05 7.6 92.5 3.13
30
2.4 2.1 4.9 20.1 13.2 0.66 0.81 22.8 24.7 12.2 1.09 8.5 94.6 3.30
3.6 4.2 9.7 20.5 13.4 0.66 0.76 23.1 26.9 12.6 1.10 8.9 95.3 3.36
4.8 6.8 15.7 20.7 13.5 0.65 0.74 23.2 28.1 12.8 1.11 9.0 95.7 3.40
40
2.4 2.0 4.6 19.4 12.9 0.66 0.90 22.5 21.6 13.8 1.14 9.9 97.8 3.54
3.6 3.8 8.8 19.8 13.1 0.66 0.84 22.7 23.5 14.3 1.16 10.3 98.7 3.61
4.8 6.2 14.3 20.0 13.2 0.66 0.82 22.8 24.6 14.5 1.17 10.6 99.2 3.64
50
2.4 2.0 4.6 18.7 12.5 0.67 1.00 22.1 18.8 15.5 1.21 11.4 101.1 3.76
3.6 3.7 8.5 19.2 12.7 0.66 0.94 22.4 20.5 16.0 1.23 11.9 102.2 3.83
4.8 6.0 13.9 19.4 12.8 0.66 0.91 22.5 21.4 16.3 1.24 12.1 102.8 3.86
60
2.4 1.9 4.4 18.0 12.1 0.67 1.11 21.8 16.2 17.2 1.27 12.8 104.5 3.96
3.6 3.5 8.1 18.5 12.4 0.67 1.04 22.0 17.8 17.8 1.30 13.4 105.7 4.02
4.8 5.8 13.4 18.7 12.5 0.67 1.01 22.1 18.6 18.1 1.31 13.6 106.4 4.06
70
2.4 1.8 4.2 17.2 11.8 0.68 1.23 21.4 14.0 18.8 1.34 14.2 107.8 4.13
3.6 3.3 7.6 17.7 12.0 0.68 1.16 21.6 15.3 19.4 1.36 14.8 109.0 4.19
4.8 5.5 12.7 17.9 12.1 0.67 1.12 21.8 16.0 19.8 1.37 15.1 109.7 4.22
80
2.4 1.7 3.9 16.3 11.4 0.70 1.36 20.9 12.0 20.3 1.40 15.6 110.8 4.27
3.6 3.2 7.4 16.8 11.6 0.69 1.28 21.2 13.1 20.9 1.42 16.1 112.1 4.33
4.8 5.2 12.0 17.1 11.7 0.69 1.24 21.3 13.8 21.3 1.43 16.4 112.7 4.35
85
2.4 1.6 3.7 15.8 11.2 0.71 1.43 20.7 11.1 21.0 1.42 16.2 112.2 4.33
3.6 3.1 7.2 16.4 11.4 0.70 1.35 21.0 12.2 21.6 1.44 16.7 113.4 4.39
4.8 5.0 11.6 16.7 11.5 0.69 1.31 21.1 12.7 21.9 1.46 16.9 114.0 4.41
90
2.4 1.6 3.7 15.3 11.0 0.72 1.50 20.4 10.2 21.7 1.45 16.7 113.5 4.39
3.6 3.0 6.9 15.9 11.2 0.71 1.42 20.7 11.2 22.2 1.47 17.2 114.6 4.44
4.8 4.9 11.3 16.2 11.3 0.70 1.38 20.9 11.7 22.5 1.48 17.4 115.2 4.46
100
2.4 1.6 3.7 14.1 10.5 0.75 1.65 19.8 8.6
Operation Not Recommended
3.6 2.9 6.7 14.8 10.8 0.73 1.56 20.1 9.5
4.8 4.8 11.1 15.1 10.9 0.72 1.52 20.3 9.9
110
2.4 1.6 3.7 12.8 10.0 0.78 1.81 19.0 7.1
3.6 2.9 6.7 13.6 10.3 0.76 1.72 19.4 7.9
4.8 4.8 11.1 13.9 10.5 0.75 1.68 19.6 8.3
Interpolation is permissible; extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. ARI/ISO certifi ed conditions are 80.6°F DB and
66.2°F WB in cooling and 68°F DB in heating.
Table does not refl ect fan or pump power corrections for ARI/ISO conditions.
All performance is based upon the lower voltage of dual voltage rated units.
Operation below 40°F EWT is based upon a 15% antifreeze solution.
Operation below 60°F EWT requires optional insulated water/refrigerant circuit (standard on residential models).
See performance correction tables for operating conditions other than those listed above.
See Performance Data Selection Notes for operation in shaded areas.
Performance capacities shown in thousands of Btuh460 CFM Nominal (Rated) Airfl ow
*WPD Adder for
Motorized Valve,
CCE19
(Cv = 4.9,
MOPD = 125 psi)
GPM
WPD Adder
PSI FT
2.4 1.17 2.71
3.6 2.88 6.64
4.8 5.53 12.77