Specifications
18
19
BONAIRE EVAPORATIVE AIR CONDITIONING
Model VSS50 VSS55 VSM60 VSM65 VSL70 VSL75
Height (mm) Front 683 683 790 790 1047 1047
Back 573 573 681 681 937 937
Width (mm) 1184 1184 1192 1192 1192 1192
Weight (kg) 61 61 65 65 80 80
Duct work (mm) 550 x 550 550 x 550 550 x 550 550 x 550 800 x 550 800 x 550
Water Conservation System
®
Standard Standard Standard Standard Standard Standard
Unit sizing.
All evaporative air conditioners vary in performance according
to the architectural features of a home and different climatic
conditions in Australia. Bonaire recommends using the Bonres
®
Unit Selection Guide as the only reliable method of determining
the cooling capacity of a Bonaire unit in your home.
BONAIRE INVERTER REVERSE CYCLE DUCTED REFRIGERATIVE AIR CONDITIONING
Model
Indoor
BI 12 BI 14 BI 18
Outdoor
Models
Outdoor Condenser unit 6650020 6650030 6650040
Reverse Cycle Indoor fan coil unit 6650021 6650031 6650041
Capacity
Rated capacity Cooling kW 12 14 18
Heating kW 13.2 15.3 18.5
Power input Cooling kW 4.35 5.07 6.08
Heating kW 4.2 4.35 5.35
Performance
Rated system air flow l/s @ High speed 639 750 1028
Rates System Static Pressure Pa 50 ~ 180 50 ~ 180 50 ~ 180
Outdoor Sound Pressure dB(A) @ 1 Mtr 61 62 68
Rated EER (Cooling) 2.76 2.77 N/A
Rated COP (Heating) 3.21 3.2 N/A
Rated AEER (Cooling) N/A N/A TBA
Rated ACOP (Heating) N/A N/A TBA
Star Rating (Cooling) 3.5 3.5 TBA
Star Rating (Heating) 4 4 TBA
Outdoor Unit Operating Range Cooling Degrees C 5 ~ 48 5 ~ 48 5~48
Outdoor Unit Operating Range Heating Degrees C (-10) ~ 28 (-10) ~ 28 (-10) ~ 28
Suitable Area M
2
@ 2.4 M Ceiling 36 ~ 60 56 ~ 93 64 ~ 110
Electrical
Power supply Voltage /Phase 240/1 240/1 415/3
Running Current Cooling Amp 22.6 26.8 16.8
Running Current Heating 21.9 24.4 15.4
Full Load Amps Amp 26.6 30 18.3
Voltage Range (Condenser Unit) 198 ~ 254 198 ~ 254 342 ~ 418
Dimensions
Outdoor unit W x H x D 950 x 1255 x 410 950 x 1255 x 410 1000x1510x400
Outdoor Unit Packaging Dimensions W x H x D 1030 x 1380 x 440 1030 x 1380 x 440 1135x1645x440
Indoor Unit W x H x D 1200 x 380 x 590 1200 x 380 x 590 1330x500x850
Indoor Unit Packaging Dimensions W x H x D 1410 x 445 x 695 1410 x 445 x 695 1588x650x1030
Gross Weight Outdoor Unit Kg 122 122 145
Gross Weight Indoor Unit Kg 63 63 118
Refrigeration System
Compressor System Dual- Fixed & Inverter Dual- Fixed & Inverter Dual- Fixed & Inverter
Refrigerant Type R410A R410A R410A
Pre Charge Pipe Length Mts 5 5 5
Pre Charge Quantity kg 3.2 3.9 8.8
Additional charge Grams/Mtr 100 100 110
Pipe Size (Liquid) mm (") 9.53 (3/8") 9.53 (3/8") 12.7 (1/2")
Pipe Size (Suction) mm (") 19.05 (3/4") 19.05 (3/4") 22.0 (7/8")
Pipe length (maximum) Mts 25 25 35
General Information
Outdoor unit colour Cream Cream Cream
Outdoor unit paint finish Powder Coated Powder Coated Powder Coated
Outdoor fan grill material UV Stabilised Ploypropelyne UV Stabilised Ploypropelyne UV Stabilised Ploypropelyne
Features
7 Day Programmable Control
4 4 4
Infra Red Remote Control
4 4 4
Auto Changeover Cooling to Heating
4 4 4
Dual Compressors
4 4 4
Optional compatable Zone System
4 4 4
The full technical data chart should be consulted for more technical detail. This product must be installed by a qualified licensed installer.
Specifications.
BONAIRE INVERTER HIGH WALL SPLIT AIR CONDITIONING
Model Number
BH35 BH52 BH70
Model indoor BHWSI35 BHWSI52 BHWSI70
Indoor part number 6700036 6700046 6700056
Model outdoor BHWSO35 BHWSO52 BHWSO70
Outdoor part number 6700035 6700045 6700055
Type Reverse Cycle Inverter Reverse Cycle Inverter Reverse Cycle Inverter
Control type Remote Remote Remote
Rated cooling capacity kW 3.7 5.2 7.0
Rated cooling capacity range kW 1.84 ~ 4.48 1.6 ~ 6.0 1.98 ~ 7.5
Rated heating capacity kW 4.0 5.6 7.5
Rated heating capacity range kW 1.3 ~ 4.8 1.4 ~ 6.8 2.1 ~ 8.5
EER (cooling) 3.41 3.04 3.06
Star rating cooling 2.3 1.6 1.6
COP (heating) 3.38 2.99 3.01
Star rating for heating 2.3 1.5 1.5
Moisture removal l/Hr 1.0 2.0 2.5
Indoor sound pressure level at 1 MTR (high speed) dB(A) 42.0 42.0 47.0
Outdoor sound pressure level at 1 MTR dB(A) 67.0 69.0 74.0
Outdoor operating temperature range Cooling 21°C ~ 43°C 21°C ~ 43°C 21°C ~ 43°C
Heating -5°C ~24°C -5°C ~24°C -5°C ~24°C
Electrical Data
Power supply 220 ~ 240VAC /50/1P 220 ~ 240VAC /50/1P 220 ~ 240VAC /50/1P
Rated current (Amps) Cooling 4.4 7.1 10
Heating 4.7 7.8 10.2
Rated input (Watts) Cooling 1010 1640 2300
Heating 1070 1800 2340
Refrigerant System
Refrigerant type R410A R410A R410A
Compressor type Rotary Rotary Rotary
Evaporator coil 3 bend 3 bend 3 bend
Condenser coil Double arranged Double arranged Double arranged
Fan system
Indoor air circulation l/s 208/222 208/222 305/305
Indoor fan motor output Watts 23 23 35
Outdoor fan motor output Watts 31 68 65
Connections
Connecting pipe - gas Inches 1/2 1/2 5/8
Connecting pipe max length Metres 15 15 15
Connecting pipe - liquid Inches 1/4 1/4 3/8
Connecting pipe max length Metres 15 15 15
Other
Suitable area M
2
15~23 25~40 30~50
Indoor dimensions (WxHxD) mm 898 x 280 x 202 898 x 280 x 202 1033 x 313 x 202
Outdoor dimensions (WxHxD) mm 760 x 552 x 256 820 x 605 x 300 900 x 805 x 360
Packaging dimensions indoor (WxHxD) mm 995 x 365 x 298 995 x 365 x 298 1103 x 400 x 300
Packaging dimensions outdoor (WxHxD) mm 863 x 598 x 376 965 x 650 x 438 1031 x 835 x 447
Gross weight indoor Kg 14 14 17
Gross weight outdoor Kg 37 46 67
Warranty – domestic 5 year parts and labour 5 year parts and labour 5 year parts and labour
*All units tested to T1 parameters
BONAIRE DUAL CYCLE SYSTEM MATCHING CHART
BI 12 BI 14 BI 18
B4 4 Star 20kW XA & 30kW 20kW XA, 30kW XA 30kW XA
B5 5 Star 21kW XA, 30kW 21kW XA, 30kW XA, 35 kW 30kW XA, 35kW