The temperature indicated on the display keeps fluctuating:
This is predominantly a display and not a thermometer indicating the temperature of the wine in the
bottles.
As explained previously, the device works in cycles and fluctuations are therefore normal and only
indicate the air temperature at a given moment.
It is based on this principle of fluctuation to the air that a consistent average temperature is
maintained in the bottles.
To check the display is functioning correctly:
Place a thermometer in the cabinet, check the temperature that it displays and compare it to the one
indicated on the display on the panel. The thermometer must be positioned at the same height as
the sensor, however there will most certainly be a difference as the sensor is enclosed.
If there is a significant difference, replace the display (only to be completed by specialist technicians).
The temperature that is usually indicated on the display no longer appears:
Replace the batteries (2 x LR44):
Procedure: remove the display, open the rear compartment, replace the batteries, close and reinsert
the display.
Be careful not to pull it down too far so as not to change the position of the sensor.
3.6 The temperature is too low
Is the device situated in an unheated environment?
Check this during the winter and ensure that the wine cabinet model is equipped with a winter
system.
How many readings were taken? How? Using what type of device?
Ensure that the value indicated is not the result of an instant reading taken while the compressor
was in operation (the internal temperatures are colder = minimum peak).
What is the local ambient temperature?
If the area is cold and the cabinet is equipped with a winter system, check the:
- Heating thermostat
- Element
And replace if necessary.