Operation Instructions
Flush valve line must be piped to atmospheric pressure such

any changes in elevation and should be sloped downward in
the direction of drainage. Do not pipe the ush or drain line
into a pressurized line.
Note: The Automatic Timer Flush Package needs to be
programmed when it is received by the end-user. The
programming is simple and takes only a few moments.
However, because every application has dierent
parameters that aect the required frequency between
ushes and the duration of the ush, the end-user must
choose the controller’s settings (refer to specic strainer
type manual).
To Program the ATF Controller
1. Plug the transformer into a 120-VAC outlet.
2. Insert the 12-VDC plug coming from the transformer
into the jack on the underside of the ATF box.
3. 

the valve will start to open).
4. 
inner timer ring with the GREEN POINTER clockwise to
increase duration. The ON TIME RANGE is factory set at

5. 
outer ring with the RED POINTER clockwise to increase
duration. The OFF TIME RANGE is factory set at twenty-

6. 
on the timer will come on and the upper light on the

the on light on the timer and the lower switch light
will come on.
Control Switch

down the manual control switch located on the front of the

can also be used to conveniently drain the water out of the
strainer before removing the conical screen element from
the strainer housing. A yellow indicator arrow on top of
the ATF valve will rotate in sync with the ball valve to show

control switch is released, the valve will automatically close.
SAFETY FIRST! - Keep ngers away from valve opening
to avoid getting caught in the moving parts. The electric
motor supplied a sucient amount of power to cause
personal injury. Take precaution when handling.
Water Resistance
The valve and controller are water-resistant, but not
water-proof. Do not install below ground level where the
component can be submerged in water. Only remove
the cover plate from the valve controller when setting or

the unit during normal operation.
Pressure Dierential Alarm Package Option

monitors and displays the strainer’s inlet and outlet




alert maintenance personnel that the strainer element

Cleaning on page 54).
Figure 25
PSID High
PSID Low
Pressure Dierential Alarm (PDA) option
Alarm Reset Button
FRONT
VIEW
LEFT SIDE
VIEW
Power To ATF
110 Volt/12 Volt DC
Wall Transformer
Visual
Alarm
Audible
Alarm
Pressure Dierential
Switch-Gauge
LED Power Indicator
Dierential
Set-Point Contact
Cover-Plate Screw (4) in Corners of
Box (DO NOT REMOVE).
Visual
Alarm
RIGHT SIDE
VIEW
TOP
VIEW
BOTTOM
VIEW
AUX Contacts
(On or O with Alarm)
Red & Black
Cable Retainer
Operation Instructions
Remove the power supply and insert the connector end into

25 above) and plug the transformer into the power source.
Standard systems are supplied with a 120V power supply to
the primary of the transformer, with an output secondary of





clogged and require immediate removal and cleaning. To


Note: It is
not recommended to set the dierential switch-gauge
higher than 10 psi. Disabling the alarm or increasing the
alarm set point could result in damage to the strainer
element and allow debris to pass into the system.
Stainless Steel Strainer Option