Shell and Tube Condenser
Factory installed cleanable shell and tube condenser with
enhanced copper tube geometry. Provides removable,
epoxy coated, water plates to facilitate cleaning. Contact
factory for application parameters.
Motorized or Manual Water Isolation Valves
and Flush Ports

provide isolation to the module for maintenance and
cleaning of evaporator and condenser heat exchangers
while adjacent modules continue normal operation. Both


Motorized condenser water valves provide head pressure
regulation for low entering condenser water temperature

Available choices include:


condenser.


valves for the condenser.

the condenser.
Hot Gas Bypass
For normal leaving chilled water temperature setpoint of
44
0
F, verify that the cut-in pressure is set at 31.5 psig. For
water and glycol systems operating at lower leaving design

approximately 4 psig above the equivalent water/glycol
temperature solution freeze point.
Pressure Dierential Flow Sensor/Switch
Field installed to prevent operation of chiller without

Manual Strainers
Field installed strainers are external to the chiller bank to

A minimum 60 mesh stainless steel screen is required to
protect both the condenser and evaporator circuit.
Automatic CS Series Strainer Package

with minimum 60 mesh stainless steel screens. Available


Water Header Bypass
Factory installed to prevent deadheading the pump, a water
header bypass may be utilized and is mandatory when using
motorized valves.
Options available for following:
Direct Return:
Motorized evaporator/condenser water
isolation valves
Motorized evaporator/manual condenser water
isolation valves
Reverse Return:
Motorized evaporator/condenser water
isolation valves
Motorized evaporator/manual condenser water
isolation valves