Control Access Display Table
Page 2 of 15 10/9/2013
Product Line: UGW
Software Version: UGW-H.08B.13
Chiller Type: COOLING 4 PIPE
LOCAL ACCESS DISPLAY TABLE
/Unit Mode:
Unit Mode unit_mode_1
Normal Run
Schedule,
NoFlo/Phas,
CHWR High,
CWS Low, Sens
Error,
NoModAvail,
Module Dwn,
Compr Dwn,
NonCritAlm,
Normal Run
FALSE
LINK(S): PREV, SYSTEM SETUP, HOME, ALARM
EVAP STATUS
Screen Display
Content BACnet Object
Default Min. Value Max. Value Editable
Evap Water Temp & Pump Status
Evp H2O In: (F)
CHWR In Temp Status chwr_stat_1
54.4 FALSE
/Evp WaterOut: (F)
CHWS Out Temp Status chws_stat_1
50.2 FALSE
Evap Flow Status:
Evap Flow SW evap_flow_1
On Off, On FALSE
Ev Pmp#1 Status:
CHW Pump 1 S/S chw_pump_1_ss_1
Off Off, On FALSE
/Ev Pmp#2 Status:
CHW Pump 2 S/S chw_pump_2_ss_1
Off Off, On FALSE
Chil Water Diff Press Sensor: (PSID)
Diff Press Cool Load diff_press_cool_load_1
8.48872 °F FALSE
LINK(S): PREV, SYSTEM SETUP, STATUS
COND STATUS
Screen Display
Content BACnet Object
Default Min. Value Max. Value Editable
Cond Water Temp & Pump Status
Cnd H2O In : (F)
CWS In Temp Status cws_stat_1
67.3 °F FALSE
/Cnd H2O Out: (F)
CWR Out Status cwr_stat_1
83.3 FALSE
Cond Flow Status:
Cond Flow SW cond_flow_1
On Off, On FALSE
Cnd Pump#1 Stat:
CW Pump 1 S/S cw_pump_1_ss_1
Off Off, On FALSE
/Cnd Pump#2 Stat:
CW Pump 2 S/S cw_pump_2_ss_1
Off Off, On FALSE
Cond Water Diff Press Sensor: (PSID)
Diff Press Heat Load diff_press_heat_load_1
8.053761 °F FALSE
LINK(S): PREV, SYSTEM SETUP, STATUS
MOT VLV OPEN/CLOSE STATUS MENU
Screen Display
Content BACnet Object
Default Min. Value Max. Value Editable
Module Mot Valve Open/Close Status
Mod1 Mot Valve Open Status:
Module 1 Open m1_open_5
On Closed, Open FALSE
Mod2 Mot Valve Open Status:
Module 2 Open m2_open_5
On Closed, Open FALSE
Mod3 Mot Valve Open Status:
Module 1 Open m1_open_5
On Closed, Open FALSE
Mod4 Mot Valve Open S
Module 4 Open m4_open_5
Off Closed, Open FALSE
Mod5 Mot Valve Open Status:
Module 5 Open m5_open_5
Off Closed, Open FALSE
Mod6 Mot Valve Open Status:
Module 6 Open m6_open_5
Off Closed, Open FALSE
LINK(S): PREV, SYSTEM SETUP, HOME, ALARM
MOD X COMP1 DATA
Screen Display
Content BACnet Object
Default Min. Value Max. Value Editable
M1C1 Suc Pr: (psi)
/ MODULE 1 COMP 1
Module 1 Comp 1 Suction
Pressure
m1_c1_suc_pres_stat_5
40.6 FALSE
Suc SuperHt: (F)
Module 1 Comp 1 Suction
Superheat
m1_c1_suc_superheat_5
8.044445 FALSE
/CH Water In: (F)
CHWR In Temp Status chwr_stat_1
54.4 FALSE
M1C1 Suc Tp: (F)
Module 1 Comp 1 Suction Temp m1_c1_suct_temp_stat_5
53.6 FALSE
/CH WaterOut: (F)
M1 Evap Leaving Temp m1_chws_temp_stat_5
51.7 FALSE
M1 VFD VoltIn:
M1 VFD Screw Input m1vfd_screw_input_1
7.53594 V 0 999 FALSE
/MainTX PIDOUT:
Module 1 Comp 1 Main TXV PID
Out
m1c1_mntx_pid_5
4.1325912 0 999 FALSE
M1C1 Dis Pr: (psi)
Module 1 Comp 1 Disch Press m1_c1_disch_pres_stat_5
99.3 0 350 FALSE
/M1C1 Dis Tp: (F)
Module 1 Comp 1 Disch Temp m1_c1_disch_temp_stat_5
110.3 FALSE
M1C1 Status:
/CD Water In : (F)
Module 1 Comp 1 Status m1_comp1_status_5
On Off, On FALSE
M1C1 Fail :
/CD Water Out: (F)
Module 1 Comp 1 Fail m1_c1_fail_1
Off Off, On FALSE
M1C1 Runtime: (h)
Module 1 Comp 1 Runtime m1_c1_rtime_1
2.3116667 FALSE
/M1C1 Cycles:
Module 1 Comp 1 Cycles m1_c1_cycles_5
1.0 FALSE
M1C1 Min Runtm:
Module 1 Compr 1 Min Run m1_c1_min_runtime_5
On Off, On FALSE
/M1C1 Min OffTime:
Module 1 Comp 1 Min Off m1_c1_minimum_off_5
Off Off, On FALSE
cdmvPIDOut:
Module 1 Cond Vlv PID Out m1_cdmv_pidout_5
0.0 0 999 FALSE
%/cdmvVDCScaleOut:
Module 1 Cond Vlv Scaled PID
Out
m1_cdmv_scaled_pidout_5
2.0 0 10 FALSE
CR3 Sol Stat:
Module 1 CR3 valve status m1_cr3_valve_status_5
Off Off, On FALSE
/ CR4 Sol Stat:
Module 1 CR4 valve status m1_cr4_valve_status_5
On Off, On FALSE
NOTE: CR3 is Unload, CR4 is Full Load.
Compressor Amps:
Module 1 Comp 1 Amps m1c1_amps_stat_5
33.6 0 999 FALSE
Page 1 of 15 10/9/2013
Product Line: UGW
Software Version: UGW-H.08B.13
Chiller Type: COOLING 4 PIPE
STANDBY
Screen Display
Content BACnet Object
Default Min. Value Max. Value Editable
ClimaCool Corp. CoolLogic
Date:
Time:
CHWS Temp:
EVAP OUT TMP chws_temp_1
50.1 °F FALSE
F CWR Temp: (F)
COND OUT TMP cwr_temp_1
83.3 °F FALSE
press any key to continue
HOME
Screen Display
Content BACnet Object
Default Min. Value Max. Value Editable
Chill Water In: (F)
CHWR In Temp Status chwr_stat_1
54.4 FALSE
/Cool Spt: (F)
Active CHW Setpoint chw_stp_stat_1
45.0 °F FALSE
Chill WaterOut: (F)
CHWS Out Temp Status chws_stat_1
50.2 FALSE
/ Tot Stg Want:
Num of Comp Requested comp_req_1
2.0 FALSE
Cond Water In : (F)
CWS In Temp Status cws_stat_1
67.3 °F FALSE
/ Tot Stg On:
Num of Comp ON comp_on_1
2.0 FALSE
Cond Water Out: (F)
/ Mode :
Mode mode_1
CLG
Cooling,
Heating
FALSE
Chil Water Flow :
/Heat Spt: (F)
Evap Flow SW evap_flow_1
On No, Yes FALSE
Cond Water Flo:
Cond Flow SW cond_flow_1
On No, Yes FALSE
/UnitMode:
Unit Mode unit_mode_1
Normal Run
Schedule, No
Flo/Phas,
CHWR High,
CWS Low, Sens
Error, No
ModAvail,
Module Down,
Compr Down,
NonCrit Alm,
Normal Run
FALSE
LINK(S): STATUS, SYSTEM SETUP, SERVICE MENU SETUP, ALARM
STATUS
Screen Display
Content BACnet Object
Default Min. Value Max. Value Editable
CoolLogic Chiller Status Menu
LINK(S): ALL MODULE COMP UNLOAD STATUS,MODULE SIZE STATUS, CHILLER OPER STATUS,EVAP STATUS, COND STATUS,MOT VLV OPEN/CLOSE STATUS MENU,
MOD1 COMP1 DATA,MOD2 COMP1 DATA,MOD3 COMP1 DATA,MOD4 COMP1 DATA,MOD5 COMP1 DATA,MOD6 COMP1 DATA,ALL COMPR RUNTIME STATUS,
ALL COMPR CYCLES STATUS,ALL COMPR SS STATUS, ALL COMPR AMPERAGE STATUS,PREV, CLOCKSET, HOME, ALARM
MODULE SIZE STATUS
Screen Display
Content BACnet Object
Default Min. Value Max. Value Editable
Module Size Status Only Legend
Mod1 Size:[
]/ 1= Not Used /4=80Ton Mod
Mod 1 Size m1_size_st_1
4.0 1 4 FALSE
Mod2 Size:[
]/NOTE:DO NOT SELECT 2 OR 3
Mod 2 Size m2_size_st_1
4.0 1 4 FALSE
Mod3 Size:[
]
Mod 3 Size m3_size_st_1
4.0 1 4 FALSE
Mod4 Size:[
]
Mod 4 Size m4_size_st_1
4.0 1 4 FALSE
Mod5 Size:[
]
Mod 5 Size m5_size_st_1
1.0 1 4 FALSE
Mod6 Size:[
]
Mod 6 Size m6_size_st_1
1.0 1 4 FALSE
LINK(S): PREV, ALARM, SYSTEM SETUP, CLOCKSET
CHILLER OPER STATUS
Screen Display
Content BACnet Object
Default Min. Value Max. Value Editable
CoolLogic Operating & Loading Status
PID1 Count:
Stage 1 Cooling PID stg1_clg_pid_1
106.719604 FALSE
/Chil WaterOut: (F)
CHWS Out Temp Status chws_stat_1
50.2 FALSE
Mod1 VFD Volt:
M1 VFD Screw Input m1vfd_screw_input_1
7.53594 V 0 999 FALSE
/Mod2 VFD Volt:
M2 VFD Screw Input m2vfd_screw_input_1
4.4 V 0 999 FALSE
Mod3 VFD Volt:
M3 VFD Screw Input m3vfd_screw_input_1
0.0 °F 0 999 FALSE
/Mod4 VFD Volt:
M4 VFD Screw Input m4vfd_screw_input_1
0.0 °F 0 999 FALSE
HPID1 Count:
Stage 1 Heating PID stg1_htg_pid_1
0.0 FALSE
/Cond WaterOut: (F)
CWR Out Status cwr_stat_1
83.3 FALSE
Cool Spt:
Active CHW Setpoint chw_stp_stat_1
45.0 °F FALSE
F / Heat Spt: (F)
Active Htg Setpoint cw_stp_stat_1
125.0 °F FALSE
Unit Stat:
Unit Status unit_status_1
On
Unit OFF, Unit
ON
FALSE
LOCAL ACCESS DISPLAY TABLE