Ultra Green Chiller Water Cooled - Model UGW Installation, Operation & Maintenance
Table of Contents Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Voltage/Phase Monitor Wiring. . . . . . . . . . . . . . . . . . . . . . . . . 20 Pre-Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Pre-Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Introduction General Description WARNING! WARNING! To avoid possible injury or death due to electrical shock, open the power supply disconnect switch and secure it in an open position during installation. The ClimaCool Ultra Green Chiller Solution, model UGW, incorporates 80 ton nominal chiller modules, with availability of up to 640 tons per bank, utilizing the most advanced technology compact quiet screw compressor, optimized for water cooled applications and non-ozone depleting R-134a refrigerant.
Pre-Installation Inspection Upon receipt of equipment, carefully check the shipment against the bill of lading and inspect each chiller for any damage incurred during shipment. Thoroughly check for any visible damage of control panels and electrical and/or refrigeration components or broken copper lines. The carrier must make proper notation of any damages or shortages on all copies of the bill of lading and complete a common carrier inspection report prior to your final acceptance of the shipment.
Unit Installation Unit Placement ClimaCool modular chillers must be installed in a conditioned and dehumidified space. The minimum foundation requirement for the chiller is a level surface capable of bearing the combined operating weight of the modules (See Physical Data on page 5).
Model Key W = Water Rejection Means 080 ₁ ₂ W ₃ 080 ₄ ₅ ₆ B ₇ F ₈ V ₉ W ₁₀ B ₁₁ C ₁₂ M ₁₃ 0 ₁₄ S ₁₅ Ultra Green Solution Model Key UG Refrigerant Options Model Configuration C = Shell & Tube Condenser S = Standard X = Special Options 0 = (None) B = Hot Gas Bypass C = Compressor Isolation Valves D = Hot Gas Bypass & Compr. Isolation Valves R = Pressure Relief Valves X = Special Options 0 = (None) B = Evap & Condsr Motorized Valves E = Evap.
Physical Data Model UGW Module and Compressor Capacity (Tons) 80 1 77 Refrigerant Type R-134a Compressor kWi 53.75 kW/Ton @ Full Load 0.698 Compressor Type Optimized Quiet Screw Compressor Quantity 1 Compressor Nominal HP 80 Refrigerant Charge (lbs) 119 Oil Circulation Rate <0.
Dimensional Data and Drawings Chilled Water Outlet Chilled Water Inlet B Condenser Water Outlet Condenser Water Inlet A Model UGW 80 C Voltage A Unit Width3 (in.) B Unit Height3 (in.) C Unit Depth3 (in.) Unit Weight 1 (lb.) Operational Weight2 (lb.) Header Connection (in.) 208/230/460/575/3/60 34 3/4 78 753/4 74 2,995 3,390 3,422 8 Notes: 1. Shipping weight includes refrigerant charge, compressor oil and packaging. 2.
Rigging and Lifting Procedures Rigging Each module should be lifted using lift straps threaded through the steel base cutouts and a spreader bar. Note: If no spreader bar is used, damage to the module may occur. Figure 1 Figure 2 Lifting Strap Lifting Strap Spreader Bar Spreader Bar Spreader Bar Lifting and Transporting Modules Pallet jacks or forklifts are required for lifting and transporting the module. Each module has base cutouts provided for ease of maneuverability.
Mounting Rail and Vibration Isolation ClimaCool recommends locking down the chiller to a concrete base or to (3) 4” base mounting rails using the six bolt holes provided in each base pan. Due to the low vibration of the modules, ClimaCool does not require the application of spring isolators or pads. Should isolators or pads be desired, install in accordance with Figures 4 and 5.
www.climacoolcorp.com 12” 36” Minimum 60” For Shell and Tube (Tube Cleaning) Front Service Access Rear Service Access Top View Notes: 1. For brazed plate, allow 36” clearance for electrical panels and 30” clearance for rear access to modules. 2. For shell and tube, allow 60” clearance for electrical panels and 30” clearance for rear access to modules. 3. Allow a minimum of 36” height clearance for service. 4. Local building or electrical codes may require additional clearance.
Water Piping ClimaCool provides four (4) temperature sensors and wells with each chiller system configured by the CoolLogic Control System. They must be field installed 36” - 60” away from the bank and before the strainer on the chilled water inlet, chilled water outlet, condenser water inlet and condenser water outlet (See Water Piping Configuration – page 12). Note: Sensors must be fully inserted into the well to obtain proper readings.
Water Piping Modules can be designated for fixed bypass for heating, cooling and source flow, however, this limits the number of modules remaining for that duty. Also, with a module acting as a bypass increased wear of heat exchangers may be caused by abrasion from bypass flow. ClimaCool offers two types of water header bypass kits, direct return (Figure 6) and reverse return (Figure 7) as shown on page 10.
Water Piping Configuration www.climacoolcorp.com Figure 9 - Field Piping Direct Return Figure 10 - Field Piping Reverse Return Notes: 1. Figures 9 and 10 are required piping for proper water regulation and distribution through ClimaCool modular chillers. 2. Module order and incoming/outgoing water flow as shown in both Figure 9 and 10 can be set up as either a left-to-right or right-to-left configuration. 3. Evaporator Hydronic Circuit shown.
Hydronic Refrigeration Figure 11 - Condenser Hydronic Circuit Circuit Figure 1 - Condenser Hydronic Leaving Condenser Water Temperature Sensor Service Ports (3/4") Refrigerant Circuit Refrigerant Circuit Isolation Ball Valves (3") Pete's Ports Heat Exchanger Figure 12 - Chilled WaterWater CircuitCircuit Figure 2 - Chilled Service Ports (3/4") Refrigerant Circuit Refrigerant Circuit Isolation Ball Valves (3") Pete's Ports Leaving Chilled Water Temperature Sensor Heat Exchanger Note: Figure 11 and 12
Filling the Water System It is imperative that the water systems are free from debris prior to initial operation. See Water Treatment for a comprehensive list of precautions on page 15. Filling, Purging and Leak Testing the System After the water systems have been properly installed, visually inspect all joints for tightness. If the chiller is to be installed in an existing system, the cleanliness of the existing system can be judged from the operating conditions of the present machines.
Water Treatment Water quality is of the utmost importance for the proper care and maintenance of the modular chiller system. Proper water treatment is a specialized industry and it is recommended to consult an expert in this field to analyze the water for compliance with the water quality parameters listed in Table 1. The materials exposed to the water are type 316 stainless steel, pure copper and carbon steel. Other materials may exist external to the ClimaCool chiller.
Water Temperature Requirements Condenser Water Temperature Chilled Water Temperature The condensers are designed to operate most efficiently at lower entering water temperatures for lower power consumption. The expansion valve, however, relies on the pressure difference across the valve to drive the liquid refrigerant through.
Condenser and Evaporator Water Pressure Drop Charts Condenser Water Pressure Drop 80-Ton, "Ultra Green" Series Model# UGW080 - Shell & Tube 100 43.3 80 34.7 60 50 45 40 35 30 25 26.0 21.7 19.5 17.3 15.5 13 20 18 16 14 12 8.7 7.8 7.0 6.1 5.2 10.8 10 4.3 8 3.5 6 2.6 4 1.7 2 0.87 1 10 30 40 60 80 100 120 140 160 200 240 280 350 180 220 260 300 400 Pressure Drop (PSI) Pressure Drop (Ft. of Water) Model# UGW080 - Brazed Plate 0.
Glycol Performance Adjustment Factors Charts 18 www.climacoolcorp.
Electrical Connection The power for all modules is taken from a suitable circuit breaker/fused disconnect power supply within the main panel. The electrical service enters the individual modules through the top into the module’s control panel enclosure. Proper grounding of the module is mandatory. Before carrying out any electrical work, confirm that the main supply is isolated. A typical power wiring is located on page 60 – Power Distribution Drawing.
Voltage/Phase Monitor Wiring 20 www.climacoolcorp.
Pre-Startup All startups must be performed by ClimaCool factory trained personnel. Prior to chiller startup, there are certain essential checks which must be completed. Failure to carry out these checks could result in damage to the chiller voiding the modules warranty. Electrical It is imperative to turn off the main electrical power supply and follow proper lock-out/tag-out procedures prior to servicing any of the chiller’s electrical components.
Pre Startup Check List (UGW-Water-Cooled) E-mail technicalsupport@climacoolcorp.com • Fax 405-815-3052 Project Name: _________________________________________________Date:_________________________ Address: ___________________________________________________________________________________ 1. Are modules connected properly per Codes and Installation Manual? (Installation, Operation & Maintenance Manual is available at www.climacoolcorp.com) YES ___ NO ___ 2.
Startup All startups must be performed by ClimaCool factory trained personnel. 1. Review all items are complete from the Pre-Startup Check List. 2. Cross reference model number with submittal sheet to verify that the units are the correct model type and voltage requirements. 3. Verify the location and wiring connections of all main header temperature sensors (should be a minimum of 36” from the bank).
Startup 18. Verify proper communications from each module back to the master controller using the “STATUS” menu, then indexing down to the desired compressor data screen. • If the compressor data parameters all read “0,” then communications are not yet established, and communications cable troubleshooting is required.
Startup & Warranty Registration Form (Water-Cooled) UGW . E-mail technicalsupport@climacoolcorp.com Fax 405-815-3052 Ambient StartupPre & Warranty Registration Form UGW Page: Temp:(Water-Cooled) Startup Check List (UGW-Water-Cooled) E-mail technicalsupport@climacoolcorp.com Fax 405-815-3052 Project Name: Contractor: E-mail technicalsupport@climacoolcorp.
Control Access Display Table The purpose of the Control Access Display Table is to assist Service Technicians with navigation through the BACview Interface Device menu structure, of which, provides an operator interface to the Status, Setup and Configuration of the menus within. Conventions used in this Manual- The following is a discussion of the conventions used to understand the navigation of this table as it relates to the information provided within the BACview Interface Device.
Control Access Display Table Editable- True = Value is adjustable. False = Value is ‘read only’. Many of the Menus in the Control Access Display Table are typical of each module, Menus for subsequent modules are not listed. To preserve space in this document, these single Menus are represented with a title of MOD X, and can be viewed, Module by Module, in the BACview Interface Device.
STATUS Content BACnet Object Screen Display Default Min. Value Max.
3 Module Mot Valve Open/Close Status Mod1 Mot Valve Open Status: Mod2 Mot Valve Open Status: Mod3 Mot Valve Open Status: Mod4 Mot Valve Open S Mod5 Mot Valve Open Status: Mod6 Mot Valve Open Status: LINK(S): PREV, SYSTEM SETUP, HOME, ALARM Module 1 Open Module 2 Open Module 1 Open Module 4 Open Module 5 Open Module 6 Open m1_open_5 m2_open_5 m1_open_5 m4_open_5 m5_open_5 m6_open_5 Content BACnet Object Module 1 Comp 1 Suction Pressure m1_c1_suc_pres_stat_5 Suc SuperHt: (F) Module 1 Comp 1 Suction S
CoolLogic Compressor Amperage Status M1C1 Compr Amps: /M4C1 Compr Amps: M2C1 Compr Amps: /M5C1 Compr Amps: M3C1 Compr Amps: /M6C1 Compr Amps: LINK(S): PREV, SYSTEM SETUP, HOME, ALARM Module 1 Comp 1 Amps Module 4 Comp 1 Amps Module 2 Comp 1 Amps Module 5 Comp 1 Amps Module 3 Comp 1 Amps Module 6 Comp 1 Amps Control Access Display Table m1c1_amps_stat_5 m4c1_amps_stat_5 m2c1_amps_stat_5 m5c1_amps_stat_5 m3c1_amps_stat_5 m6c1_amps_stat_5 33.6 0.4 25.4 0.0 0.4 0.
3 Manual Rotate LeadCompr: Rotate Cmpr Lead on Runtime Hrs : Refresh Runtime Hours: Stage Down Safety Index: (sec) Stage Up Safety Index: (sec) LINK(S): PREV, SYSTEM SETUP, HOME, ALARM Manually Refresh Lead Module Lead Swap on Runtime Control Access Display Table man_refr_modlead_1 Do Not Do Not Rotate, Refresh Lead Rotate lead_swap_runtime_1 runtime_refresh_4 safety_ind_delay2_4 safety_ind_delay1_4 168.
/M3C1Reset Alm? /M2 Frz-CWReset? M4 VFD in Alarm? M2 in CWR Alm? (/) /M4C1Reset Alm? M5 VFD in Alarm? M3 inFreezAlm? /M5C1Reset Alm? /M3 Frz-CWReset? M6 VFD in Alarm? M3 in CWR Alm? (/) /M6C1Reset Alm? LINK(S): PREV, SYSTEM SETUP, HOME M4 inFreezAlm? /M4 Frz-CWReset? RESET MODULE FREEZ & HOT ALARMS M4 in CWR Alm? (/) Screen Display CoolLogic Reset Mod Freez &Hot Alarms M5 inFreezAlm? M1 inFreezAlm? /M5 Frz-CWReset? /M1 Frz-CWReset? M5 in CWR Alm? (/) M1 in CWR Alm? (/) Mod 3 Reset VFD Fault Reset Mot2 Vlv
3 3 MODULE FACTORY SETUP FN6 Screen Display Content BACnet Object Default Min. Value Max.
LINK(S): LINK(S): PREV, PREV, SYSTEM SYSTEM SETUP, SETUP, HOME HOME COMPR COMPR MIN MIN MAX MAX RUN RUN TIMES TIMES Screen Screen Display Display Compressor Min & Max Compressor Min & Max Run Run Times Times Compr Compr Minimum Minimum Run Run Time Time (sec) (sec) Compr Minimum Minimum Off Off Time Time (sec) (sec) Compr LINK(S): PREV, PREV, ALARM, ALARM, SYSTEM SYSTEM SETUP, SETUP, CLOCKSET LINK(S): CLOCKSET Content Content BACnet BACnet Object Object Default Default Min. Min. Value Value Max. Max.
3 3 Calibrate Water Diff Press Sensors Cool Water Dif Psi Stat: (PSID) Cool PsiCalib Offset: (PSID) Heat Water Dif Psi Stat: (PSID) Heat Psi Calib Offset: (PSID) Diff Press Cool Load Chilled Diff Press Calibration Point diff_press_cool_load_1 chwpsi_cali_point_1 8.48872 °F Diff Press Heat Load diff_press_heat_load_1 Cond Diff Press Calibration Point cwpsi_cali_point_1 8.053761 °F 0.0 Control Access Display Table FALSE -199 199 TRUE FALSE 0.0 -199 199 TRUE Min. Value Max.
VFD Minimum VDC: In 3 Scr: 6.16 Cond Wat In Lock VFD Minimum VDCValue In 4 Scr: Cond Wat In Lock : (F) 7.17 VFD VDC Input: 10.
3 3 Clg PID Rise Slow: (%/min) Clg PID Fall: (%/min) Cool Deadbd1: /CoolDeadbd2: Stage One Cool PID I-Gain#2: PID Switching Differential: (%) Cool Cntrl Setpt Offset: (F) LINK(S): PREV, ALARM, SYSTEM SETUP, CLOCKSET Clg PID Rise Slow Clg PID Fall Clg PID DB1 Clg PID DB2 Clg PID IG2 PID Differential Factor Cool Control Setpoint Offset clg_rise_slow_1 clg_fall_1 clg_db1_1 clg_db2_1 clg_ig2_1 pid_diff_fact_1 cl_cntrl_spt_offset_1 5.0 sec 22.0 0.3 0.0 0.01 5.0 0.
Mod5 Mot Valve Signal to Close: Mod6 Mot Valve Signal to Close: Delay Before Closing Mot Valves: Open Ext Bypass if NO Comps ON? Module 5 Closed Module 6 Closed Delay Before Closing Mot Vlv Open Bypass Valves by NO Comps ON m5_closed_5 m6_closed_5 close_vlv_delay_5 open_byp_vlv_on_no_cmps_1 Cool Header Ext Bypass Valve Heat Header Ext Bypass Valve cl_hdr_ext_byp_vlv_1 ht_hdr_ext_byp_vlv_1 Content BACnet Object Input Chnl 10 Type inp_10_point_type_1 Min Cond Wat Out Setpt: (F) Max Cond Wat Out Setpt
3 Cond Wat In Lo Limit: (F) Hot Max CondWtr Wat OutScale@5V,10Vor20mA: Lo Limit: (F) Cond Wat MinCond Dif PrWater Flo Setpt: (PSI) Main Header Hi Limit: Chil Min DifOut Pr Flo Setpt: (PSI) (F) CWRWat Cond Wtr UGW Hi Limit: Differential Pressure Sensure Readings: CWS Cond Wtr In UGW Hi Limit: (F) Cond WaterWtr DiffOut Press Sensor: (PSID) CWR Cond UGH Hi Limit: (F) Chil Diff Press Sensor: (PSID) CWSWater Cond Wtr In UGH Hi Limit: (F) LINK(S): PREV, Cond Wat In Hi SYSTEM Limit: (F)SETUP, HOME LO CND LVG TMP
CoolBin 30% (h)SETTINGS MAIN TXV PID / CoolBin 80% (h) Screen Display CoolBinTXV 40% (h)Settings MAIN PID /M1C1 CoolBin 90% (h) MainTXV PID Output: (%) CoolBin 50% (h) /CoolBin 100% (h) M2C1 MainTXV PID Output: (%) Reset Hours in ALL Cool Bins: LINK(S): PREV, SYSTEM SETUP, M3C1 MainTXV PID Output: (%)HOME, ALARM COOL BIN 20-30 % HRS COOL BIN 70-80 % HRS Content COOL BIN 30-40 % HRS COOL BIN 80-90 % HRS TXV PID Module 1 Comp 1 Main COOL Out BIN 40-50 % HRS COOL BIN 90-1001%Main HRSTXV PID Module 2 Comp COOL
3 M3C1 MainTXV PID Output : M2C1 MainTXV Min Dif PID Output : M3C1 MainTXV Superht PID Output : Main TXV Max Suct PSI STPT: M3C1 MainTXV Max Suc PID Output : Module PID Out 3 Comp 1 Main TXV PID m3c1_mntx_pid_5 Out Module 2 Comp 1 Main TXV PSI m2c1_mntx_scaled_psidif_pidout_5 Module 3 Comp 1 Main TXV m3c1_mntx_scaled_spht_pidout_5 DIF PID Out SPHT TX PIDMaximum Out Main Suct PSI mntx_maxpsi_stpt_5 M4C1 MainTXV Output : M3 & M4 MAIN TXVPID SETTINGS Screen Display M4C1 MainTXV Superht : Modules 3 & 4 MAI
Chiller Operation and Maintenance Pressure and Temperature Log A log of temperatures and pressures should be taken regularly. Periodically conduct a visual inspection of the chiller to identify problems before they reach the point of failure. As with any mechanical system, it is necessary to conduct a series of checks to confirm correct operation of the chiller. Maintaining a Daily Log Date Chiller No.
Heat Exchangers Draining When performing standard maintenance procedures such as flushing a heat exchanger, it will be necessary to close off a section of a module. This can easily be done if factory mounted water isolation valves are provided. Access to a floor drain is helpful when performing standard maintenance procedures. Back Washing It may become evident from the recorded weekly log data that the performance of the chiller is gradually degrading.
Cleaning Arrangement Figure 1 - City Water Cleaning Arrangement Figure 14 - City Water Cleaning Arrangement Service Port (3/4") Connect to City Water To Cooling Tower Header Isolation Ball Valves (2, 2 ½ or 3") Refrigerant Circuit Pete's Ports Header Refrigerant Circuit From Cooling Tower Connect to Drain Service Port (3/4") Heat Exchanger Figure 15 - In Place Cleaning Arrangement Figure 2 - In Place Cleaning Arrangement Cleaning Pump Service Port (3/4") To Cooling Tower Header Isolation Ball Va
Operational Limitations Voltage Limitations The following voltage limitations are absolute and operation beyond these limitations may cause serious damage to the compressor.
Compressor Information Model UGW utilizes a screw compressor. The compressor is highly efficient and extremely reliable. The information contained in this manual will be useful for care and maintenance. Compressor Rotation All screw-type machines are unidirectional and will only compress in one direction. Operating in the reverse rotation will be destructive and will be indicated by a load operating noise together with a lack of compression.
Refrigeration Circuit Diagram CHILLER WATER PIPING CONDENSER WATER PIPING CHILLER OUTLET WATER MAIN (8") GROOVED CONDENSER OUTLET WATER MAIN (8") GROOVED CHILLER INLET WATER MAIN (8") GROOVED CHILLER WATER OUTLET VALVE (WHEN USED) CONDENSER WATER OUTLET VALVE (WHEN USED) CHILLER WATER INLET VALVE S3 (WHEN USED) 5 FILL SHUT-OFF VALVE 10 FILL SHUT-OFF VALVE (WHEN USED) CONDENSER WATER INLET VALVE (WHEN USED) (WHEN USED) FLUSH SHUT-OFF VALVE CONDENSER INLET WATER MAIN (8") GROOVED 9 7 (WH
Refrigeration System Re-Processing and Charging Conforming to local and national codes is the responsibility of the service technician or installing contractor. The service technician should be familiar with the following codes: • ASHRAE Standard Safety Code for Mechanical Refrigeration, ANSI/ASHRAE 15-1978 • American National Standard Code for Pressure Piping, ANSI B31.5-1974 reaches zero psig or slightly higher. Then, repeat the entire evacuation process described above.
Refrigeration System Re-Processing and Charging Operation This valve is a step motor operated electric expansion valves. Step motors are designed to provide discrete segments of angular motion, or rotation, in response to an electronically generated signal. The step motor used in this valve is a 12-volt DC, two-phase, bi-polar, permanent magnet rotor type. Motor rotation is converted to linear motion by the use of a lead screw and threaded drive coupling.
Refrigeration System Re-Processing and Charging Interface Board Factory installed interface board allows externally supplied control signals to control electronic expansion valve. Figure 18 - Interface Board The routine will require approximately 8 seconds for the interface board 1, 16 seconds for the interface board 2 and interface board 3 and 32 seconds for the interface board 6. The valve will not respond to input signals during this time.
Refrigeration System Re-Processing and Charging Test the Valve The resistance of the motor winding may be tested without opening the system. 1. Remove power from the external controller and/or interface board. 2. Remove the valve leads from interface board. 3. Measure the resistance between the black and white leads of the valve. Resistance should be 75 ohms with the valve at room temperature or approximately 65 ohms if the valve is at -40°F. 4.
Options and Accessories Shell and Tube Condenser Water Header Bypass Factory installed cleanable shell and tube condenser with enhanced copper tube geometry. Provides removable, epoxy coated, water plates to facilitate cleaning. Contact factory for application parameters. Factory installed to prevent deadheading the pump, a water header bypass may be utilized and is mandatory when using motorized valves.
Stainless Steel Strainer Option Figure 20 - Stainless Steel Strainer Strainer Installation Recommendations The following the guidelines are recommended when installing the strainer: 1. 2. 3. Safety Considerations Prior to installation, this manual must be read carefully and all instruction understood. Personal injury or product damage can occur if the following safety precautions are overlooked or ignored.
Stainless Steel Strainer Option Table 2 Table 1 Figure 21 - Recommended Torquing Sequence Strainer 3CS 4CS 6CS 8CS 10CS Bolt Size Recommended Torque (ft. lbs) 5/16 3/8 1/2 1/2 5/8 - 60 15 45 45 80 (inches) 18 16 13 13 11 - 80 25 55 55 100 Note: The 3CS strainer torque is in lbs (not ft. lbs). Strainer Operation Periodically, it will be necessary to flush out the debris that is collected and settles to the bottom of the strainer reservoir.
Stainless Steel Strainer Option What Causes Water Hammer? Figure 22 Any action that can cause a rapid change in the velocity of the flow can set off a water hammer, such as closing a downstream valve, pump stoppage, etc. Typically, for short lengths of pipe (below 500 feet) downstream valves that are closed within 1/10th of a second can generate a water hammer. What Can Water Hammer Do? Pressure spikes from water hammer can raise fluid pressures to dangerously high values.
Stainless Steel Strainer Option Operation Instructions Water Resistance Flush valve line must be piped to atmospheric pressure such as an open floor drain. The flush line should not undergo any changes in elevation and should be sloped downward in the direction of drainage. Do not pipe the flush or drain line into a pressurized line. The valve and controller are water-resistant, but not water-proof. Do not install below ground level where the component can be submerged in water.
Stainless Steel Strainer Option When the differential set point is reached, both the audible and visual alarms will be triggered. It will remain engaged until both the alarm condition is corrected and the alarm-reset button is pressed (if the alarm-reset button is pressed but the differential pressure is beyond the set point, the alarms will re-engage immediately). After the strainer is cleaned and put back in service, the differential pressure should return to 1 psi.
“Y” Strainer Basket Strainer Before installing the “Y” strainer, ensure the pressure rating is correct for the system. If the end connections are threaded or designed for soldering or brazing, be sure the piping is straight and not at an angle or offset. If the strainer has flanged ends, be sure the flanges of the connecting IOM-MS-YStrainers piping are square with the pipe so that no undue stress is put on the strainer or piping when tightening the flange bolts.
94.8 75.9 460/3/60 575/3/60 UGW080 UGW080 95 119 255 150 200 450 (MOP)3,8 Size MaxFuse 125 150 350 Size Fuse 4,8 Rec. 150 200 400 Size9 Switch Discon. 75.2 94.0 208.1 Amps1 Load Rated 94 118 260 (MCA)2 Amps Min.Cir. 300 350 782 (LRA)5 Rotor Locked 150 200 450 (MOP)3 Size MaxFuse Internal Wiring - per Compressor 125 150 350 Size Fuse4 Rec. www.climacoolcorp.
Power Distribution Drawing Figure 26 Notes: 1. Breaker panel represents field power supply and is to be installed by others. Not provided as part of the ClimaCool modular chiller system. 2. Breaker panels can be supplied for skid mount pump/tank packages or new construction projects as options. Consult your local ClimaCool Representative. 3. Control wiring by others. 4. Field connections are simplified requiring only a two-conductor shielded cable daisy chain from the master controller to the modules.
Wiring Diagram 61 www.climacoolcorp.
Wiring Diagram 62 www.climacoolcorp.
Troubleshooting Guide WARNING! The troubleshooting guidelines recommended in this section could result in exposure to electrical safety hazards. Please refer to the safety warnings provided in this manual. Failure to follow all of the recommended safety warnings provided could result in death or serious injury. When possible, disconnect all electrical power including remote disconnects before servicing. Follow proper lockout‐tagout procedures.
Troubleshooting Guide Compressor Cycle On High Pressure Control Possible Cause Remedy Main condenser water valve closed or restricted Open valve to full open position. Module condenser water isolation valves, if Open valves to full open position. provided, closed or restricted Water regulating valve incorrectly set Reset or replace. or defective Compressor discharge valve partially closed Open valve to full open position.
www.climacoolcorp.com forms\ccool\standard forms\word files\CCool warranty compressor certificate 07-11-13 Please refer to the CC Installation, Operation and Maintenance Manual for operating and maintenance instructions. NOTE: Some states or Canadian provinces do not allow limitations on how long an implied warranty lasts, or the limitation or exclusion of consequential or incidental damages, so the foregoing exclusion and limitations may not apply to you.
15 S. Virginia Oklahoma City, OK 73106 Phone: 405-815-3000 Fax: 405-815-3052 www.climacoolcorp.com ClimaCool works continually to improve its products. As a result, the design and specifications of each product at the time for order may be changed without notice and may not be as described herein. Please contact ClimaCool’s Customer Service Department at (405) 815-3000 for specific information on the current design and specifications.