User Manual
45
www.climacoolcorp.com
Electrical Data UCW
Rated Min.Cir. MaxFuse Rec. Discon. Rated Min.Cir. Locked MaxFuse Rec.
Load Amps Size Fuse Switch Load Amps Rotor Size Fuse
Amps
1
(MCA)
2
(MOP)
3, 4
Size
4,5
Size
6
Amps
1
(MCA)
2
(LRA)
7
(MOP)
3
Size
5
UCW030AHASASB0S
208-230/3/60 85 96 125 110 150 42.7 53.3 425 90 70
UCW030AFASASB0S
460/3/60 39 43 60 50 70 19.3 24.1 187 40 30
UCW030ANASASB0S
575/3/60 31 35 50 40 50 15.4 19.3 148 30 25
UCW050AHASASB0S
208-230/3/60 147 166 225 200 225 73.7 92.1 500 150 125
UCW050AFASASB0S
460/3/60 67 75 100 90 100 33.3 41.7 250 70 60
UCW050ANASASB0S
575/3/60 53 60 80 70 80 26.7 33.3 198 50 45
UCW070AHASASB0S
208-230/3/60 190 214 300 250 300 95.1 118.9 600 200 150
UCW070AFASASB0S
460/3/60 86 97 125 110 150 43.0 53.8 310 90 70
UCW070ANASASB0S
575/3/60 69 77 110 90 110 34.4 43.0 255 70 60
UCW085AHASASB0S
208-230/3/60 225 253 350 300 350 112.4 140.5 732 250 175
UCW085AFASASB0S
460/3/60 102 115 150 150 175 50.8 63.5 368 110 80
UCW085ANASASB0S
575/3/60 82 92 125 110 125 40.7 50.8 292 90 70
Notes:
7. LRA - Locked Rotor Amps are instantaneous starting amperage per compressor.
Power Wiring - per Module
UCW030
UCW050
UCW070
4. MOP Device or Recommended Fusing Device for Module Power Wiring supplied by others. These are recommended values for electrical power protection of modules selected.
Internal Wiring - per Compressor
6. Disconnect Switch for Module Power Wiring supplied by others. These are recommended values for electrical power protection of modules selected.
Model
Type
Model #
Voltage
5. Recommended Dual Element Fuse Sizing: Rounded up from 150% of the RLA of the largest compressor motor plus 100% of the RLA of all other concurrent electrical loads.
UCW085
575V / 60 Hz: Min. 518V Max. 632V
8. Module internal wiring is per NEC.
9. Voltage Tolerance Range:
208-230V / 60 Hz: Min. 187V Max. 253V
460V / 60 Hz: Min. 414V Max. 506V
2. MCA - Minimum Circuit Ampacity is: 125% of the RLA of the largest compressor motor plus 100% of the RLA of all other concurrent motors and/or electrical loads.
1. RLA - Rated Load Amps are calculated as per UL1995.
3. MOP - Maximum Overcurrent Protected Device Amp Size is rounded down from: 225% of the RLA of the largest compressor motor plus 100% of the RLA of all other concurrent electrical loads.