Instruction Manual
www.climacoolcorp.com
22
PreStartUp R-410A PkgAirCool Rev. 0
ProjectName:_________________________ Date:___________________
Address: _________________________
_________________________
YES NO
1.
Aremodulesconnectedproperly“perCodesandInstallationManual? ____ ____
(Installation,Operation&Maintenance Manualisavailableatwww.climacoolcorp.com)
2. Istherea60Ͳ80meshstrainerontheevaporatorinletwater? ____ ____
(FillwatertoChillerbeingsuretopassthrough60Ͳ80meshstrainer.)
3. Ischilledwatersystemfilled,flushedandallairpurgedfromsystem?________
(Allairmustbepurgedfromsystempriortostartup.SeeFillingtheWaterSysteminIO&M)
4. Areallpumpstestedandoperational?________
5. ArerequiredGPM’s(verifiedbypressuredifferential)suppliedtotheChiller? ____ ____
(SeeprojectspecificationsorselectionandperformancesheetsavailablefromClimaCoolSalesRep)
6. Pressuredifferentialflowsensor/switchsettotripondropbelowrequiredflows? ____ ____
(Settotriponlowflow(lessthan75%flow),notpumpon/off.)
7. HaveallChillercouplingconnectionsbeenleaktested?____ ____
8. Istherewaterpresentlycirculatingthroughchiller?____ ____
9. Verifiedthattemperaturesensorsandvoltage/phasemonitorhavebeeninstalled? ____ ____
10. Verifiedpowersupplyagreeswithchillernameplate?____ ____
11. Ispower
andcommunicationwiringcompletetoeachmodule?____ ____
12. Verifythatwiringanddevicesmeetwithapprovedelectricalsubmittaldrawings?____ ____
13. IsrequiredloadavailabletorunmultiplecompressorsatstartͲup? ____ ____
14.Iscondenserfunctionaltomaintaincondenserrequiredoperation? ____ ____
(Thisincludesmaintaining“minimum”inlettemperature.See“OperationalLimitations”inIO&M”.)
Ifyouchecked“No”toanyquestionabove,providethelinereferencenumberandthedateofscheduledcompletion
below.PleasenoteallconditionsmustbecompletepriortothestartͲupdate.
__________________________________________________________________________________________________
_
__________________________________________________________________________________________________
_
*ThisformmustbecompletedandsubmittedtoClimaCoolCorp.two(2)weekspriortofinalschedulingofanyStartͲup.
Note:IfanyoftheaboveitemsarenotcompleteattimeofstartͲup,backchargeswillbeassessedforadditionalcosts.
ContractorName:___________________________
Address:___________________________
___________________________
Phone:___________________________ _________________________________
(AuthorizedSignature)
PreStartͲUpCheckList* (PackagedAirͲCooled)
EͲmailcustomerservice@climacoolcorp.com
orFaxto:405Ͳ745Ͳ2072