Table 1 - Performance Adjustment Factors vs. Altitude vs. Chiller Temperature Drop
Chiller
Water
Temp.
°F
Capacity
Multiplier
Flowgpm
Multiplier
kWPower
Multiplier
Capacity
Multiplier
Flowgpm
Multiplier
kWPower
Multiplier
Capacity
Multiplier
Flowgpm
Multiplier
kWPower
Multiplier
Capacity
Multiplier
Flowgpm
Multiplier
kWPower
Multiplier
8 0.995 1.246 0.998 0.990 1.244 1.003 0.986 1.238 1.006 0.980 1.232 1.012
10 1.000 1.000 1.000 0.993 0.997 1.004 0.989 0.990 1.007 0.983 0.996 1.014
12 1.005 0.834 1.001 0.996 0.831 1.004 0.992 0.826 1.008 0.986 0.821 1.016
14 1.010 0.716 1.001 0.998 0.714 1.005 0.994 0.709 1.009 0.989 0.704 1.018
SeaLevel 2000ft. 4000ft. 6000ft.