Instruction Manual

15
www.climacoolcorp.com
Filling the Water System
It is imperative that the water systems are free from debris
prior to initial operation. See Water Treatment - page 16 for
a comprehensive list of precautions.
Filling, Purging and Leak Testing the System
After the water system has been properly installed, a visual
inspection should be made to all joints for tightness. If
the chiller is to be installed in an existing system, the
cleanliness of the existing system can be judged from the
operating conditions of the present machines. The cooling
tower in particular should be inspected and cleaned if
required. It is a good practice to at least ush the existing
system and ideally, to acid wash the system before
connecting a new chiller.
The following sequence is recommended to ll and leak
check the water system for modules WITHOUT Water
Isolation Valves:
1. Ensure that all drain valves are closed and that all main
water header isolation valves (external to the system)
are opened.
2. All modules are equipped with 3/4” ll and ush valves
with lines teed into the inlet and outlet connections into
and out of the heat exchanger. Ensure these 3/4” valves
are CLOSED.
3. The system should be lled with clean water sent
through a strainer and the system checked for leaks.
4. Once the main water lines and the chiller headers are
lled with clean water, purge and repeat the lling
process several times.
5. Following the nal lling and leak checking procedure,
air should be purged from the system.
The following sequence is recommended to ll and leak
check the water system for modules WITH Water Isolation
Valves:
1. Close all water isolation valves inside each module
which isolate the individual heat exchanger.
2. Ensure that all drain valves are closed and that all water
main isolation valves (external to the system) are
opened.
3. The system should be lled with clean water sent
through a strainer and the system checked for leaks.
4. Once the main water lines and the chiller headers are
lled with clean water, purge and repeat the lling
process several times.
5. All modules are equipped with 3/4” ll and ush valves
with lines teed into the inlet and outlet connections into
and out of the heat exchanger. Ensure these 3/4” valves
are CLOSED.
6. Open the water isolation valves inside each modular
chiller and repeat the lling process, this time also
checking for leaks inside each module.
7. Following the nal lling and leak checking procedure,
air should be purged from the system.
Cleaning the System
The following sequence is recommended to properly clean
the water systems:
1. Whenever possible, install a temporary bypass line
between the main supply and return water header of
the chilled water system prior to cleaning the system.
Open the main header bypass lines to divert the initial
water ow around the module heat exchanger until you
are con dent the circulating water is mostly pure.
2. Provided the main header bypass lines are installed,
close all water isolation valves inside all modules
equipped with manual or automatic water isolation
valves. If the modules are NOT equipped with water
isolation valves, we recommend installing 3-way main
header bypass valves so the initial water ow bypasses
all module heat exchangers.
3. The pumps should be run with the strainer in place (see
Starting the Pumps section for proper pump startup).
All external hydronic branches should be open to all
devices in the system.
4. After several hours of operation, the strainer should
be isolated and cleaned. Repeat until there is no more
debris being collected by the strainer.
5. Open all water isolation valves inside each module
equipped with manual or automatic water isolation
valves (see step 6 for modules NOT equipped with
water valves). If bypass lines are not installed as
described in step 1 above, it is recommended to drain
out the initial ll of water to help ush out debris.
Finally, close o the main header bypass lines referred
to in step 1 above, and open the ow to the main water
headers. Repeat steps 3 and 4 until there is no more
debris being collected by the strainer.
6. If bypass lines are not installed as described in step
1 above, and if the modules are NOT equipped with
water isolation valves, it is recommended to drain out
the initial ll of water to help ush out debris. Before
re lling and purging the system again, the strainers
should be removed and cleaned. Repeat steps 3 and
4 until there is no more debris being collected by the
strainer.
Starting the Pumps
Follow the manufacturer’s recommendations when starting
the pumps for the rst time. The system should be checked
for leaks and air purged with the pumps in operation. The
pressure drop across the heat exchangers will give a good
indication of ow through the system (See page 17 - 18 –
Evaporator Water Pressure Drop Charts). This should be
immediately checked against the expected pressure drop
for the ow rate required. If the pressure drop begins to
fall and the ow rate is falling, this could indicate a need to
clean the strainers.