Electrical Data - 60 Hz
The ClimaCool
®
Modular Chiller -
Electrical Data -
Models 30, 50 & 65 - FLEX SeriesFLEX SeriesFLEX
NOTES:
1. RLA. Rated Load Amps are calculated as per UL1995.
2. MCA. Minimum Circuit Ampacity: 125% of the RLA of the largest compressor motor plus 100% of the RLA (or FLA) of all
other concurrent motors and/or electrical loads.
3. MOP. Maximum Overcurrent Protection or Max.Fuse Sizing: Rounded down from 225% of the RLA of the largest compressor
motor plus 100% of the RLA (or FLA) of all other concurrent electrical loads.
4. Recommended (Dual Element) Fuse Sizing: Rounded up from 150% of the RLA of the largest compressor motor plus 100% of
the RLA (or FLA) of all other concurrent electrical loads.
5. Locked Rotor Amps are instantaneous starting amperage per compressor.
6. Module internal wiring is per NEC.
7. Voltage Tolerance Range:
208-230V / 60Hz: Min. 187V Max. 253V
460V / 60Hz: Min. 414V Max. 506V
575V / 60Hz: Min. 518V Max. 632V
8. MOP Device or Recommended Fusing Device for Module Power Wiring supplied by others.
These are recommended values for electrical power protection of modules selected.
LEGEND:
RLA - Rated Load Amps
LRA - Locked Rotor Amps
MCA - Minimum Circuit Amps
MOPD - Maximum Overcurrent Protection Device
Model Voltage Power Wiring - per Module Internal Wiring - per Compressor
FLEX RLA
1
MCA
2
MOP
3,8
Rec. Fuse
4,8
RLA
1
MCA
2
LRA
5
Fuse Size
4
30 208-230/3/60 92 103 125 125 46 58 425 70
30 460/3/60 42 47 60 60 21 26 187 35
30 575/3/60 33 37 50 45 17 21 148 30
50 208-230/3/60 142 160 225 200 71 89 500 110
50 460/3/60 64 72 100 90 32 40 250 50
50 575/3/60 51 58 80 70 26 32 198 40
65 208-230/3/60 183 206 250 250 92 115 600 150
65 460/3/60 83 93 125 110 41 52 310 70
65 575/3/60 66 75 100 90 33 41 255 60
DANGER
!
Electric shock hazard!
May result in injury or death!
Disconnect power supply(ies)
before servicing!
Refer servicing to qualified
service personnel.
Risque de choc électrique!
Résultat de mai dans dommages
ou la mort!
Debrancher avant d’entreprendre
le dépannage de l’appareil!
Consulter un réparateur qualifie
pour le dépannage.
DANGER
!
The ClimaCool
®
Modular Chiller -
Electrical Data -
Models 30, 50 & 65 - FLEX SeriesFLEX SeriesFLEX
NOTES:
1. RLA. Rated Load Amps are calculated as per UL1995.
2. MCA. Minimum Circuit Ampacity: 125% of the RLA of the largest compressor motor plus 100% of the RLA (or FLA) of all
other concurrent motors and/or electrical loads.
3. MOP. Maximum Overcurrent Protection or Max.Fuse Sizing: Rounded down from 225% of the RLA of the largest compressor
motor plus 100% of the RLA (or FLA) of all other concurrent electrical loads.
4. Recommended (Dual Element) Fuse Sizing: Rounded up from 150% of the RLA of the largest compressor motor plus 100% of
the RLA (or FLA) of all other concurrent electrical loads.
5. Locked Rotor Amps are instantaneous starting amperage per compressor.
6. Module internal wiring is per NEC.
7. Voltage Tolerance Range:
208-230V / 60Hz: Min. 187V Max. 253V
460V / 60Hz: Min. 414V Max. 506V
575V / 60Hz: Min. 518V Max. 632V
8. MOP Device or Recommended Fusing Device for Module Power Wiring supplied by others.
These are recommended values for electrical power protection of modules selected.
LEGEND:
RLA - Rated Load Amps
LRA - Locked Rotor Amps
MCA - Minimum Circuit Amps
MOPD - Maximum Overcurrent Protection Device
Model Voltage Power Wiring - per Module Internal Wiring - per Compressor
FLEX RLA
1
MCA
2
MOP
3,8
Rec. Fuse
4,8
RLA
1
MCA
2
LRA
5
Fuse Size
4
30 208-230/3/60 92 103 125 125 46 58 425 70
30
460/3/60 42 47 60 60 21 26 187 35
30
575/3/60 33 37 50 45 17 21 148 30
50
208-230/3/60 142 160 225 200 71
89 500 110
50
460/3/60 64 72 100 90 32
40 250 50
50
575/3/60 51 58 80 70 26
32 198 40
65
208-230/3/60 183 206 250 250 92
115 600 150
65
460/3/60 83 93 125 110 41
52 310 70
65
575/3/60 66 75 100 90 33
41 255 60