CHILLER OPERATION AND MAINTENANCE
Pressure and Temperature Log
A log of temperatures and pressures should be taken
regularly. Periodically conduct a visual inspection
of the chiller to identify problems before they reach
the point of failure. As with any mechanical system,
it is necessary to conduct a series of checks to the
ClimaCool chiller to confirm correct operation.
Daily
A daily operational log should be kept
Perform visually inspection
Record entering and leaving chilled water and
condenser water temperatures and pressures
Note any problems that may exist. Immediately
plan for further investigation. If repair is necessary,
schedule for earliest possible date.
Properly document all data taken
Weekly
Review daily log from previous week
Perform visual inspection
Properly document all data taken
Note any problems that may exist. Immediately plan for
further investigation. If repair is necessary, schedule for
earliest possible date.
Quarterly
Check controller operating parameters and set points
Check refrigerant pressures and temperatures
Check compressor amps
Check compressor oil level
Check and test all safeties
Check water flow rates and pressure drops across
evaporator and condenser
Properly document all data taken
Annual
Isolate chiller, drain all water circuits
Back flush all heat exchangers (use only ClimaCool
recommended de-scalers)
Remove and clean all waterside strainers
Perform leak test on all refrigerant circuits
Check all interconnecting flanges for proper
tightness
Perform oil analysis on each compressor
Check and test all refrigerant safeties for proper operation
Check all electrical terminal connections for tightness
Manually operate all waterside isolation valves on each
module
Check all peripheral systems for proper operation
Check and test main controller
Verify set points, sensors and general configuration
Properly document all data taken
HEAT EXCHANGERS
Back Washing
It may become evident from the recorded daily log data that
the performance of the chiller is gradually degrading. This
could be due to a buildup of debris or sludge obstructing the
free passage of flow through the heat exchangers. This debris
can be removed by a "back washing" process, which involves
the introduction of a forced, violent, backwards flow through
the heat exchanger, using a carefully formulated flushing
solution. To be effective, this back flow should be slightly
Chiller Operation and Maintenance
1
www.climacoolcorp.com
Recommended Maintenance Schedule
Pressure and Temperature Log
A log of temperatures and pressures should be taken regularly. Periodically conduct a visual inspection of the chiller to
identify problems before they reach the point of failure. As with any mechanical system, it is necessary to conduct a
series of checks to the ClimaCool
®
chiller to confirm correct operation.
Maintaining a Daily Log
Date _______
Data Log ___________________
Chiller No.
______
Technician
___________________
Sun. Mon.
Tue. Wed. Thu. Fri.
Sat.
Chilled Water
Entering Temp.
Chilled Water
Leaving Temp.
Condenser Water
Entering Temp.
Condenser Water
Leaving Temp.
Chilled Water
Pressure Drop
Condenser Water
Pressure Drop
Faults: Note By
Module Number
Daily
A daily operational log should be kept
Perform visually inspection
Record entering and leaving chilled water and
condenser water temperatures and pressures
Note any problems that may exist. Immediately
plan for further investigation.
If
repair is
necessary, schedule for earliest possible date.
Properly document all data taken
Weekly
Review daily log from previous week
Perform visual inspection
Properly document all data taken
Note any problems that may exist.
Immediately plan for further investigation.
If
repair is necessary, schedule for earliest
possible date.
Quarterly
Check controller operating parameters and set
points
Check refrigerant pressures and temperatures
Check compressor amps
Check compressor oil level
Check and test all safeties
Check water flow rates and pressure drops
across evaporator and condenser
Properly document all data taken
Annual
Isolate chiller, drain all water circuits
Back flush all heat exchangers (use only
ClimaCool
®
recommended de-scalers)
Remove and clean all waterside strainers
Perform leak test on all refrigerant circuits
Check all interconnecting flanges for
proper tightness
Perform oil analysis on each compressor
Check and test all refrigerant safeties for
proper operation
Check all electrical terminal connections for
tightness
Manually operate all waterside isolation valves
on each module
Check all peripheral systems for proper
operation
Check and test main controller
Verify set points, sensors and general
configuration
Properly document all data taken