User guide
www.climacoolcorp.com
®
19
when handling.
Automatic Timer Flush ATF-EA-1.5 (optional)
Valve Specifications
A. Water-resistant Polypropylene Motor Case
B. High Torque Motors with Perma-lube Gears
C. Open & Close Indicator
D. Stainless Steel Ball Valve & Hardware
E. Auto Reset Circuit Breaker
F. 90 Degree Bidirectional Rotation
G. Controller Case
Fig. 3
Automatic Timer Flush Package Option
TROUBLESHOOTING: If you require further assistance, please call us at (405) 745-3185.
PROBLEM POSSIBLE CAUSE SOLUTION
• Valve is leaking past ball • Seals damaged or worn out • Install repair kit
• Valve is not stopping at proper • Adjust limit switches
closed position
• Valve stem leaks • Worn stem seals • On metal valves: tighten stem packing
nut 1/2 turn.
CAUTION! Over tightening stem nut
could cause drag on motor and trip
internal circuit breaker. May require
repair kit or new valve.
• Valve body leaks • Loose body bolts or excessive operating • Check bolts and observe recommended
pressure ratings
• Defective seals • Install repair kits or new valve
• Valve hard to turn • Swollen seals or product buildup in valve • Check valve for compatibility with
chamber product, may require valve cleaning or
new valve
• Valve bolts too tight • Loosen bolts slightly
• Stem nut too tight • Loosen stem nut slightly