Recommended Clearances
1 Allow 36” clearance for electrical panels and 24” clearance for rear service access to modules
2 Allow a minimum of 18” height clearance for service and 12” for side clearances
3 Local building or electrical codes may require additional clearance Consult applicable codes
Modular Chiller Bank Dimensions - w/Connnection Flange Gaskets and Blank Off Plates
Model Dimensions
AR2 Width (ft/ inches) Depth (inches) Height (w / o panels) Height (w / panels)
25 & 30 50 65 25 & 30 50 65 25 & 30 50 65 25 & 30 50 65
1 module 2’ 7-1/8” 2’11-1/8” 2’11-1/8” 45-5/8” 46-7/8” 46-7/8” 72-7/8” 76-3/4” 76-3/4” 77” 78-3/8” 78-3/8”
2 modules 5’3/4” 5’ 8-3/4” 5’ 8-3/4” 45-5/8” 46-7/8” 46-7/8” 72-7/8” 76-3/4” 76-3/4” 77” 78-3/8” 78-3/8”
3 modules 7’ 6-3/8” 8’ 6-3/8” 8’ 6-3/8” 45-5/8” 46-7/8” 46-7/8” 72-7/8” 76-3/4” 76-3/4” 77” 78-3/8” 78-3/8”
4 modules 10’ 0” 11’4” 11’4” 45-5/8” 46-7/8” 46-7/8” 72-7/8” 76-3/4” 76-3/4” 77” 78-3/8” 78-3/8”
5 modules 12’ 5-5/8” 14’1-5/8” 14’1-5/8” 45-5/8” 46-7/8” 46-7/8” 72-7/8” 76-3/4” 76-3/4” 77” 78-3/8” 78-3/8”
6 modules 15’7/8” 17’7/8” 17’7/8” 45-5/8” 46-7/8” 46-7/8” 72-7/8” 76-3/4” 76-3/4” 77” 78-3/8” 78-3/8”
7 modules 17’ 6-1/2” 19’ 10-1/2” 1 9’10-1/2” 45-5/8” 46-7/8” 46-7/8” 72-7/8” 76-3/4” 76-3/4” 77” 78-3/8” 78-3/8”
NOTES:
1 Modular chiller bank width dimensions above include (1/8”) between modules, plus (1 -1/2”) for required blank off plate anges
when piping for a direct return (Refer to Water Piping Conguration - Figure 1) Example: (5) AR2-65 modules 167-1/2” width +
1-1/2” (Blank off plates) + 5 x 1/8” (ange connection gaskets) = 169-5/8” (14’ 1-5/8”)
2 When piping 1 to 5 or more than 5 modules, use reverse return (Refer to Water Piping Conguration - Figure 2) Example: (7)
AR2-30 modules 206-1/2” width + 1-1/2” (Blank off plates left) + 1-1/2” (Blank off plates right) + 8 x 1/8” (ange connection
gaskets) = 210-1/2” (17’ 6-1/2”)
ClimaCool Service Clearances
The ClimaCool Modular Chiller -
Service Clearances