Troubleshooting Guide
COMPRESSOR CYCLES ON HIGH PRESSURE CONTROL
Possible Cause Remedy
1 Compressor discharge valve partially closed 1 Open valve fully
2 Non-condensable gases in hydronic system 2 Purge non-condensable gases from bleed valve on condenser or at bleed
valve of the building condenser water system
3 Overcharge of refrigerant (R-22 or R-407C) 3 Purge refrigerant from system while in operation until the rst sign of
bubbles are shown in sight glass Add back refrigerant just until bubbles clear
4 Air temp entering condenser too high 4
5 Insufcient air ow thru condenser 5 Check fan blade operation and condenser for debris
6 Fouled air cooled condenser entering face 6 Clean entering face of air cooled condenser
7 Defective high pressure switch 7 Replace
8 Non-condensable gases in refrigerant 2 Purge refrigerant from system, properly evacuate, recharge with new
refrigerant
CAUSES AND PREVENTION OF FREEZE-UP
Possible Cause Prevention
1 Improper charging 1 Charge per manufacturer’s recommendation
2 Improperly set low pressure freeze ctrl 2 Check the safety time delay low pressure control for proper setting at the
beginning of each season
3 Operating with LPC bypassed 3 The safety time delay low pressure control is wired in series with the
compressor motor contactors (Do not bypass it)
4 Improper chilled water circulation 4 Use an ample sized cleanable strainer in the chilled water circuit Make
certain in the strainer is clean to insure full ow and velocity of chilled water
It may sometimes be necessary to treat the water to prevent
formation of deposits
5 Not draining for winter shutdown 5 When the system is shut down for the winter, remove the drain plugs and
drain the cooler Blow out remaining water with air
6 Improper setting of low water temp control 6 Check setting of (freeze-stat) temperature control