Application Parameters
Performance Multipliers & Pressure Drops
Table AM-6
Performance Adjustment Factors vs. Altitude vs. Chiller Temperature Drop
Chiller Sea Level 2000 ft. 4000 ft. 6000 ft.
Water Temp.
Capacity
Flow, gpm kW Power
Capacity
Flow, gpm kW Power
Capacity
Flow, gpm kW Power
Capacity
Flow, gpm kW
Drop (
o
F)
Multiplie
r
Multiplier Multiplier
Multiplier
Multiplier Multiplier
Multiplier
Multiplier Multiplier
Multiplier
Multiplier Multiplier
8 0.995 1.246 0.998 0.99 1.244 1.003 0.986 1.238 1.006 0.98 1.232 1.012
10 1.000 1.000 1.000 0.993 0.997 1.004 0.989 0.99 1.007 0.983 0.996 1.014
12 1.005 0.834 1.001 0.996 0.831 1.004 0.992 0.826 1.008 0.986 0.821 1.016
14 1.010 0.716 1.001 0.998 0.714 1.005 0.994 0.709 1.009 0.989 0.704 1.018