THE CLIMACOOL MODULAR CHILLER
APPLICATION PARAMETERS
Water Flow Rates
It is imperative that minimum and maximum water ow rates
are not exceeded Minimum and maximum water ow rates are
dened in the Physical Data tables of this manual A ow switch
or differential pressure switch is required to conrm ow This
device is supplied by others during initial installation
Chilled Water Temperature Limits
ClimaCool air-cooled remote modules are designed for a leaving
chilled water temperature range from 42°F to 59°F All cataloged
modules can operate safely in this range without the need of
special controls or glycol additives Leaving water temperatures
below 42°F can result in evaporator suction temperatures below
the freezing point of water Therefore, we recommend a glycol
solution additive that will protect the evaporator from freeze ups
at lower operating suction temperatures
Water Quality Parameters
Proper care should he given to maintaining a clean system
Foreign matter such as scale, dirt and corrosion material can
severely affect system performance Such matter may also cause
blockage which increases water pressure drop and reduces
water ow Due to the regional differences of water conditions,
ClimaCool recommends that a local water treatment specialist
be contacted to determine a proper water treatment program
ClimaCool does not recommend the use of salt or brackish water
in chilled water systems Both have a detrimental effect on the
life of system components ClimaCool modules use a 0001
(ft2-hr oF/Btu) fouling factor for the evaporator in determining
performance ratings See page 15 for Water Treatment guidelines
Water Piping Practices
As with any water system, it is important that the system be
clean If care is taken during installation, the possibility of dirt
related problems are avoided in future operation of the chiller
The pipe work installer must remove weld scale- rust and
contamination during pipe work fabrication There are certain
necessary components that should always be installed in the
chilled water loop (see Water Piping Congurations on page
11 in this manual) Isolation valves are required in the position
shown to isolate the chiller for maintenance It is also desirable
and a good practice to have valves isolating the pumps
Refer to the ClimaCool modular chiller water piping
congurations (Figs. I and 2 on page 11) for piping
congurations on multiple modules. Before nal piping
connections are made to the chiller, all external water piping
must be thoroughly ushed. Sufcient insulation should be
installed and sealed to prevent condensation and reduce heat
gain. Chilled water volume can be accommodated with the
use of expansion tanks.
Remote Condenser Location
It is vital to select a suitable location for your remote air cooled
condenser in order to allow sufcient air ow into the cavity of
the condenser It is important not to place the condenser into a
“pit”, unless the pit is not any deeper than the condenser height
plus 10 feet, and there is at least a clearance of 2 times the width
of the unit on both sides in between the condenser and the pit
walls The unit must also be level in relation to the pit opening
AIR FLOW
1”
Min.
W”
Min.
W”
Min.
Multiple units can be placed next to each other, side by side, as
long as there is at least one width distance between them, that
being the width of the largest unit
Condensers can be located near fences, as long as there is approx
50% free area in the fence and the unit is no closer than one
width distance from the fence
Application Parameters