Remote Condenser Installation Guidelines
55
The ClimaCool
®
Modular Chiller -
Module Condenser & Hydronic Configuration
)LJXUH5HPRWH&RQGHQVHU
)LJXUH&KLOOHG:DWHU&LUFXLW
Heat Exchanger
Refrigerant Circuit #1
Refrigerant Circuit #2
Isolation Ball Valve (2”)
Service Port (3/4”)
Isolation Ball Valve (2”)
Service Port (3/4”)
Chilled Water Outlet
Chilled Water Inlet
Sensor Well (internal)
Cap Tube to Low Limit
Protection Thermostat
Header
Header
NOTES:
'RWWHGOLQHLQ)LJXUHGHSLFWVÀHOGSLSLQJWRUHPRWHDLUFRROHGFRQGHQVHU/LTXLGOLQHGULHUVLJKWJODVVDQGUHFHLYHUDUHIDFWRU\SLSHG
+RWJDVOLQHVDQGOLTXLGOLQHVWRDQGIURPWKHUHPRWHFRQGHQVHUDUHÀHOGSLSHG
2. Figure 2 depicts hydronic chilled water piping in each ClimaCool
®
chiller module.
U-BEND OR
2 ELLS
PITCH
"U"-BEND or
(2) STREET ELLS
PITCH
MODEL AR2
MODULAR
CHILLER
HOT GAS
DISCHARGE
LINE DUAL-
RISER ASSY.
MODEL RAC2
REMOTE AIR-COOLED
CONDENSER
NOTES:
1. LIne A" is
only used for systems with hot gas bypass. See chart
above for line sizes for 15 and 25 ton circuits. Line "A" is size
d to
carry the oil at minimum load condition
s.
2. Line "B" incorporates inverted "p"-traps as sho
wn, with additional
"p"-traps each addit
ional 15 feet of rise, up to 50 ft. max. See chart
above for line size
s.
3. Line "C" is for horizontal hot gas lines and
carries the full flow.
See chart above for line size
s.
4. The liquid
li ne " D" s hould incorporate a check va lve fo r
applications where the condenser is at a lower temp
erature than the
receiver, to p
revent refrigerant migration during the off-cycle. See
chart above for line siz
es.
5. All pitches are 1/8" per foot downward in the di
rection of the
refrigerant f
low.
6. One refrigerant circu it is shown. There are
two separa te
refrigerant circuits for each AR2 modul
e.
A
B
CHECK
VALVE
`
CHECK
VALVE
PITCH
C
HAND
VALVE
HAND
VALVE
ACCESS FITTINGS
FOR HEAD
PRESSURE FAN
CYCLING CONTROL
D
LIQUID
LINE
LINE SIZING CHART FOR EQUIV. PIPING RUNS UP TO 100 FEET LONG
LINE "A" LINE "B" LINE "C" LINE "D"
12 & 15-TON CIRCUITS W/OUT
HOT GAS BYPASS NOT 1-3/8" 1-3/8" 1-1/8"
(REF. AR2025 & AR2030) USED
12 & 15-TON CIRCUITS
W/ HOT GAS BYPASS 7/8" 7/8" 1-3/8" 1-1/8"
(REF. AR2025 & AR2030)
25 & 32-TON CIRCUITS W/OUT
HOT GAS BYPASS NOT 1-5/8" 1-5/8" 1-3/8"
(REF. AR2050 & AR2065) USED
25 & 32-TON CIRCUITS
W/ HOT GAS BYPASS 1-1/8" 1-1/8" 1-5/8" 1-3/8"
(REF. AR2050 & AR2065)
ClimaCool
®
Module Hydronic Configuration
Remote Condenser