Manual
26
www.climacoolcorp.com
®
PRE-START UP
Before the chiller is started, there are certain essential checks
which must be carried out Failure to carry out these checks could
result in damage to the chiller voiding the warranty
Electrical
It is imperative to turn off the main electrical power supply and
follow proper lock-out, tag-out procedures prior to servicing any
of the chiller’s electrical components The following procedures
can be performed only after the electrical power is conrmed to
be off:
1 The installation should have been inspected and approved by
the respective agent and found to be in compliance with all
local and national electrical codes
2 Check & tighten as required all electrical terminal connections
on each module Utilize lock-out/tag-out procedures for this
operation A systematic tightening of all terminals inside the
electrical control panel on each module should be carried
out This will include the compressor motor terminals, which
would require removal of the compressor terminal cover
Check connections at each safety and every termination in the
panel
3 There are approx (12) control wires which must be eld
connected from each module’s electrical panel back to the
“Master Control Panel” These control wires should be routed
using a series of twisted pair conductors having #18 AWG
minimum up to 50 ft, #16 AWG minimum up to 100 ft, and
#14 AWG min up to 250 ft All eld wiring must be identied
(tagged)
4 All eld connections should be checked for tightness
5 Check all fuses for proper sizing as indicated on the chiller
data plate and/or the electrical diagram on the inside door of
the electrical panel
Refrigeration
1 Remove the front and rear access covers from the top
compressor sound enclosure of each module
2 Refrigerant piping and components should be inspected for
damage
3 Check all refrigeration and water valves for proper
positioning; once completed mark refrigerant valves with
permanent marker Make sure all refrigerant valves are fully
opened and there are no visible signs of refrigerant leaks Pre-
Start Up
4 Place refrigerant gauges on the discharge and suction access
ports of each refrigerant circuit to ensure a refrigerant charge
is present Leave the gauges on for compressor rotation check
5 Conrm the settings on all pressure switches and thermostats
Water System
1 Conrm that leak testing has been carried out
2 Conrm that the system is clean
3 Conrm that necessary water treatment systems are in place
with both the evaporator and condenser water systems
4 Conrm that appropriate water analysis has been conducted
by the end-user
5 Conrm that the results of this water analysis does not conict
with the acceptable constituent ppm levels as indicated in
Table 1, page 16
6 Extract a water sample from both the evaporator and
condenser Conrm that the sample bottles are lled to the top
leaving no air in the bottles Both sample bottles must have
labels lled out per instructions included with bottles Mail
bottles immediately to the appropriate water testing laboratory
as per instructions included with bottles
7 Conrm that both the chilled water and condenser water
circulating pumps are operational and water is owing
through both exchangers
8 Shut entering water valve and blow out some water to check
for particles or coloration from suspended particles Record
the differential pressures across the chiller condenser water
header and across the condenser heat exchanger, measured at
the “Pete’s” ports at each module
9 Conrm correct water ow rates through the condenser
and evaporator Acquire the “predicted” ow rates from
the building’s “hydronics system balancer” Compare the
measured differential pressures from step 6 above with the
predicted ow rates to ensure proper correlation to the ow
results
Chiller Pre-Start-Up Procedures
1 Turn selector switches on module panel off Fill in circuit
# and power panel identication inside each Module cover
panel
2 Ensure the correct fuses are installed in the control
transformer fuse blocks inside each ClimaCool Module Turn
on the power to each module The “Power” light should be on
3 Override output with DX commissioning program or place
a jumper between compressor 1 start terminals on the “eld
wiring” terminal strip (terminals 8 &9) With jumper in
place, turn on the selector switch marked “compressor #1”
to bump the compressor and check for proper rotation
Use pressure gauges to verify proper rotation Once this is
complete and correct rotation is veried, override output
with DX commissioning program or place a jumper between
compressor 2 start terminals on the control terminal strip
(terminals 10 & 11) Turn on the switch marked “compressor
#2” to bump the compressor and verify that circuit #2
Pre-Start Up