Manual
24
www.climacoolcorp.com
®
When the differential set point is reached, both the audible and
visual alarms will be triggered and will remain engaged until both
the Alarm condition is corrected, and the Alarm-Reset button is
pressed (If the Alarm-Reset button is pressed but the differential
pressure is beyond the set point, the alarms will re-engage
immediately)
After the strainer is cleaned and put back in service, the
differential pressure should return to 1 PSI
If you have any questions about the Pressure Differential Alarm
option, please call our technical product specialists at (405)
745-3185
General Information
Auxiliary Contacts:
The PDA option is equipped with a remote alarm feature The
remote alarm contacts are located at the two Black & Red Banana
Clip Posts (see illustration) The alarm can be set up in one of
two ways: 1) a remote alarm signal of 12 VDC can be sent to a
central monitoring station, or, 2) a set of auxiliary contacts will
indicate a "closed" condition when the alarm activates (See
auxiliary Contact Schematic inside PDA Box) Remove the (4)
screws on the cover plate and to access the schematic located
inside the cover plate) If you have any additional questions
please contact a ClimaCool technical representative at (405) 745-
3185
Water Resistance:
The Pressure Differential Alarm Controller is water-resistant, but
not water proof Do not install below ground level where the box
can be submerged in water DO NOT REMOVE the cover plate
from the PDA Controller Keep the cover tightly sealed on the
module during normal operation
ClimaCool Corp. Return Policy:
Units in need of warranty repair, and less than 90 days old, must
be returned to ClimaCool accompanied by a Return Material
Authorization (RMA) number To request a RMA, number
call (405) 745-3185, then enter this number on the RMA form
(available from the ClimaCool web site)
Please Follow Environmental Note:
All PDA Controllers sent to ClimaCool for repair must be
cleaned and dried from all foreign residue or the shipment
will be returned “as is” to the customer We cannot expose our
technicians to the vast variety of chemicals used around our
systems Thank you for your cooperation
Maintenance:
The alarm functions of the PDA alarm package should be
checked twice a year Manually trip the differential set-point
(see illustration) to engage the audible and visual alarms
Reset the differential setting and depress the alarm-reset
button to verify the alarms are deactivated
Pressure Differential Alarm Package