Automatic Timer Flush (AFT) Package
The ATF-EA-15 ush valve package provides an automatic
method for ushing away the debris collected In the strainer’s
reservoir The power supply and timer controls for the valve
package are housed inside the ATF control box The ATF controls
can be preprogrammed to set the ushing duration and the time
interval between ushes
System Components:
A Timer Based Valve Controller (see Fig 1) sets the ush
duration (length of the ush) and the ush interval (time
between ushes)
B Electric Ball Valve: designed for dirty water use (see Fig
1 & 2)
Fig 1
A
GREEN POINTER
INNER RING
(LENGTH OF FLUSH)
(FACTORY SET AT
8-SECONDS)
RED POINTER
OUTER RING
(TIME BETWEEN
FLUSHES)
(FACTORY SET AT
24-HOURS)
Fig 2
B
12VDC@2.5A POWER
FROM PDA OR 120V PLUG
IN TRANSFORMER
OPEN/CLOSE
INDICATOR
COVER-PLATE SCREWS
(4) IN CORNERS OF BOX
(TIMER BASED VALVE
CONTROLLER)
CONTROL SWITCH
Automatic Timer Flush Package
Operation Instructions:
Flush valve line must be piped to atmospheric pressure such as an
open oor drain The ush line should not undergo any changes
in elevation and should be sloped downward in the direction of
drainage DO NOT PIPE THE FLUSH OR DRAIN LINE INTO
A PRESSURIZED LINE
Note: The Automatic Timer Flush Package Needs To Be
Programmed When It Is Received By The End-user The
programming is simple and takes only a few moments However,
because every application has different parameters that affect the
required frequency between ushes and the duration of the ush,
the end-user must choose the controller’s settings (refer to your
specic strainer manual)
To program the ATF Controller:
Plug the transformer into a 120-VAC outlet Insert the 12-VDC
plug coming from the transformer into the jack on the underside
of the ATF box Test for power by pressing the manual ush side
of the control switch (lower switch light should come on and the
valve will start to open) Adjust the “ON-TIME” (Valve Open)
by turning the inner timer ring with the GREEN POINTER
clockwise to increase duration (“ON-TIME” RANGE, See Fig
1) Adjust the “OFF-TIME” (Valve Close) by turning the outer
ring with the RED POINTER clockwise to increase duration
(“OFF-TIME” RANGE, See Fig 1) Set the control switch to auto
ush The red off light on the timer will come on and the upper
light on the switch will come on and stay on During the ush
cycle the on light on the timer and the lower switch light will
come on
Control Switch: (see illustration)
Control switch ushing is initiated by pressing and holding
down the manual control switch located on the front of the
controller The manual ush control switch can also be used to
conveniently drain the water out of the strainer before removing
the conical screen element from the strainer housing A yellow
indicator arrow on top of the ATF Valve will rotate in sync
with the ball valve to show the valve position (open or closed)
When the manual ush control switch is released, the valve will
automatically close\