Step 5: Wash all matter from the strainer gaskets and clean the
inner-ring where the bottom of the strainer element rests
Step 6: Make sure the U-shaped gasket is tted securely to the
bottom of the strainer element Reposition the strainer element
into the body of the strainer
Step 7: Make sure the strainer head gasket is secure on the top of
the strainer body On V-Band models, O-rings should be seated
completely in the body ange Reposition the strainer lid back on
the strainer body Tighten the lid securely either with the bolts or
with the band-clamp
For band-clamp models, opening and closing is achieved
without adjusting the lock nut It is tightened at the factory
to the correct compression (Minor tightening may be
necessary if the gasket loses memory over time) To open the
clamp, depress the safety latch and pull the over-center lever
outward To close the clamp, make sure the T-Bolt is seated
in its receiver and push the overcenter lever back toward
the strainer housing Be sure that the safety latch is engaged
before putting the module to use
What Is Water Hammer?
Water hammer is a phenomenon that can occur in uid systems
with long pipes Water hammer is a rapid change of pressure
caused by a rapid change in velocity If the ow has been
abruptly shut off downstream, the pressure in the entire system is
raised very quickly
What Causes Water Hammer?
Any action that can cause a rapid change in the velocity of the
ow can set off a water hammer, such as closing a downstream
valve, pump stoppage, etc Typically, for short lengths of pipe
(below 500 ft), downstream valves that are closed within 1/10th
of a second can generate a water hammer
What Can Water Hammer Do?
Pressure spikes from water hammer can raise uid pressures to
dangerously high values These pressure spikes can cause serious
damage to valves, pipes, strainers, joints, etc The ClimaCool
Strainer is rated to an absolute maximum pressure of 150 PSI
for bolted lid models, and 125 PSI for band clamp lid models
A water hammer pressure spike that raises the pressure higher
than the maximum rated pressure may result in strainer damage,
voiding the manufacturers warranty
What Can I Do To Prevent Water Hammer?
There are certain precautions that can be taken to prevent or
decrease the effect of water hammerThe addition of a surge
tank or accumulator tted with a suitable pressure relief valve
and strategically located within the water system may provide
adequate protection against the effects from water hammer
Careful attention should be given to the design and control
strategy for valves and pumps so their actions do not invite a
water hammer
Strainer