ClimaCool CS STRAINER
Fig 1
Safety Considerations
Read this manual carefully Personal injury or product damage
can occur if the following safety precautions are overlooked or
ignored We strongly recommend that you follow these safety
precautions and avoid the potential hazards listed below when
operating and maintaining your strainer:
1 After unpacking your strainer, carefully inspect your strainer
housing, lid assembly and screen for damaged or missing
parts Contact our customer service representatives for
replacement parts
2 The strainer should not be modied or used in a manner not
consistent with the manufacture’s recommendations If there
are any questions regarding its application or installation,
contact ClimaCool customer service
3 The strainer lid or pressure gauges should not, be removed
under ANY circumstance while the strainer is pressurized
4 Standard bolted lid models should never exceed 150 PSI
V-Band clamp models should never exceed 125 PSI
5 Install back-ow prevention devices (or check valves) both
upstream and downstream of the strainer to prevent back ow
or vacuum effects which can cause damage to the strainer
housing or screen
6 Install properly sized pressure relief valves both upstream and
downstream of the strainer This will help prevent Strainer
damage to the strainer and screen in the event that water
ow is stopped abruptly, or if water hammering occurs The
pressure relief valves should be set to relieve pressure at
12 times the strainer’s maximum operating pressure (not to
exceed the max rated pressure) Consult your local dealer or
pressure relief valve manufacturer to obtain properly sized
valves for your application
Note: At No Time Should The Internal Pressure Exceed The
Maximum Rated Pressure For Your Strainer
Installation Recommendations
We recommend following the guidelines below when installing
your strainer:
1 The ClimaCool Strainer should be placed on a rm,
supporting surface Failure to do so can cause stress on the
weld joints The weight of the ClimaCool Strainer should not
be supported by the main water line’s connecting it
2 The inlet and outlet connections should be securely fastened
The arrows clearly depict ow direction (see g 1)
3 The back-mount pressure gauges should be installed in the
gauge ports located on the front of the strainer body These
gauges will allow you to monitor the pressure differential
across the strainer screen providing an indication when the
strainer element is clogged and requires cleaning
4 The ClimaCool Strainer lid must be securely fastened
according to the following torque specications to ensure
product safety and an adequate seal
Torque Specications
CLAMPED LID MODELS: ClimaCool Strainer models CS-2,
CS-3, and CS-4C have “over-center latch clamp” lid designs The
over-center clamp does not require adjustment when installing or
removing the lid The lock washer is set at the factory for proper
clamp compression and normally requires no eld adjustment
Minor tightening may be necessary over time The lids are
installed as follows:
1 Place the clamp around the strainer lid
2 Latch the T-bolt with the receiver, and push the latch handle
towards the strainer body until the safety catch engages
Strainer