Instruction Manual

27
ClimaCool Electrical Data - 60 HZ
N
O
TES:
1.
RLA. Rated Load Amps are calculated as per UL1995
.
2.
MCA. Minimum Circuit Ampacit
y
: 125% of the RLA of the largest compressor motor plus 100% of the RLA (or FLA) of all
other concurrent motors and/or electrical loads
.
3.
MOP. Maximum Overcurrent Protection or Max.Fuse Sizing: Rounded down from 225% of the RLA of the largest compressor
motor plus 100% of the RLA (or FLA) of all other concurrent electrical loads
.
4
.
Recommended (Dual Element) Fuse Sizing: Rounded up from 150% of the RLA of the largest compressor motor plus 100% of
the RLA
(
or FLA
)
of all other concurrent electrical loads
.
5
.
Locked Rotor Am
p
s are instantaneous startin
g
am
p
era
g
e
p
er com
p
ressor
.
6
.
Module internal wiring is per NEC
.
7.
Voltage Tolerance Range
:
208-230V / 60Hz: Min. 187V Max. 253
V
460V / 60Hz: Min
.
414
V
Max
.
506
V
575V / 60Hz: Min. 518V Max. 632
V
8.
MOP Device or Recommended Fusing Device for Module Power Wiring supplied b
y
others.
T
hese are recommended values for electrical power protection of modules selected.
LE
G
END
:
RL
A
-
Rate
d
Loa
d
Amps
LR
A
-
Locked Rotor Amp
s
M
CA
- Minimum Circuit Amp
s
M
O
PD - Maximum Overcurrent Pr
o
tecti
o
n Devic
e
Model Voltage Power Wiring - per Module Internal Wiring - per Compressor
FLEX RLA
1
MCA
2
MOP
3,8
Rec. Fuse
4,8
RLA
1
MCA
2
LRA
5
Fuse Size
4
2
08-230/3/6
0
92
1
03
1
2
5
1
2
5
46
58
42
5
70
3
0
460/3/6
0
42
4
7
60
60
2
1
26
18
7 3
5
30
5
75/3/6
0
33
37
50
45
17
2
1
1
4
8
3
0
50
2
08-230/3/6
0
142
160
2
2
5
2
0
0
71
89
5
0
0
11
0
50
460/3/6
0
64
72
1
0
0
90
3
2
40
250
50
50
5
75
/
3
/
6
0
5
1
58
80
70
26
3
2
198
40
65
2
08-230/3/6
0
183
2
0
6
250
250
92
11
5
6
0
0
150
65
460/3/6
0
8
3
9
3
1
2
5
110
4
1
5
2 31
0
70
65
5
75/3/6
0
66
75
1
0
0
90
33
41
255
6
0
www.climacoolcorp.com
®