A) SYMPTOMS OF WATER LEVEL CONTROL RELATED PROBLEMS:
1) Boiler overfills or floods
2) Boiler dry fires (system underfills or doesn't fill)
3) Boiler doesn't fill at all
4) Water fill solenoid chatter
5) Heater contactor chatter
6) Fills but cuts out on LOW WATER before filling again
7) Overfills but does not heat
8) Fills but does not heat
B) POSSIBLE CAUSES:
1) Inoperative water level control circuit board (P/N 23198)
2) Incorrect or damaged wiring to probes
3) Incorrect or damaged wiring from water level board to loads
4) Damaged probes
5) Probes shorted together
6) Scale build-up on probes
C) FAULT ISOLATION PROCEDURE:
Equipment Required: Volt/Ohmmeter (VOM) or Multimeter
STEP
TEST
RESULT
REMEDY
1. Is power applied to the control circuit
board? Measure
Yes Go to Step #2
L1-L2 at the board to be 120 VAC + 15V. No Correct external supply problem
2. Remove two AC power wires from control
board and connect ohmmeter to control
Yes Reconnect power and go to Step #3
board power terminals. Is resistance
between 100-1000 ohms?
No Replace control board P/N 23198
(inoperative transformer)
3. Visually inspect probe wiring for damaged
or broken wires or loose or missing
terminals at either end. Is wiring visually
OK?
Yes
No
Go to Step #4
Replace wiring as required