User manual
Table Of Contents
- Table of Contents
- Installation
- Operation
- Cleaning
- Service Parts
- 20.20 Gas Generator with Cleaning
- 20.20 Gas Injection with Cleaning
- Component Panel, Gas (OGB 20.20)
- Control Panel, with Picto (all models)
- Outer Base (OGB 20.20)
- Water Hose System, Condenser (all models)
- Water Valve (all models)
- Water Valve (OGB 20.20)
- Water Valve (OGS 20.20)
- Burner Insert, HL, Pre-mounted (all Gas models)
- Burner Insert, Air, LP & Natural Gas (all Gas models)
- Pump, Steam Generator, Gas, 110V (all Gas models)
- Door (20.20 models)
- Sliding Plate (all models)
- Exterior Sheeting (all models)
- Maintenance
◊ The gas valve is energized allowing gas and air into the burner chamber to
be ignited by the hot surface igniter.
◊ The Hot Air Burner Control Module (N20) senses at least 1.5 micro amps
DC from the flame sensor (P1) at terminal 3 of connector X2 and sends a
signal from terminal 2 of connector X1 to terminal 12 of connector X15
on the Control Board (A10)
• The heat circuit will remain energized until the cabinet set temperature is
reached as sensed at probe B6.
e The steam circuit is energized.
• 120 VAC is sent from terminal 4 of connector X12 on the Control Board
(A10) to the coil of the Y3 solenoid allowing water to be thrown against the
element until the bypass probe (B5) senses 183 degrees F.
• The heat circuit will remain energized until the cabinet set temperature is
reached
f If the bypass probe (B5) drops below the set level the steam circuit will start again
g When the condensate box is heated to 140 degrees F at the B3probe, 120 VAC is
sent from terminal 5 of connector X12 to the condenser valve (Y1) until the
temperature drops.
h When the timer counts to 0 or the core temp probe (B10) reaches the set amount
the cycle ends and the steam generator reverts to the standby temperature of 190-
degree F.










