R Series Data Center Products User’s Guide, Rev. B Appendix A – Specifications • 83
Table 10 R4300 Chassis Specifications
Connections
8-slot chassis
Hot-swappable modules provide Ethernet, C/Port, and USB connections
Backwards compatible with Direct Connect or Blade Switching BackPack
Fit 14 chassis (112 PC blades) in a single 42U rack or cabinet
Four variable-speed exhaust fans located in rear
Rear power connection
Dimensions
3U (5.25" high, standard 19" rack width)
17.0"(w) x 5.25"(h) x 29.8"(d)
Power Input
Dual AC input
100–240 VAC, 50/60 Hz, dual redundant PSUs
Power supplied to each individual PC blade slot
1440 W power required per full chassis (max.)
12 Amps current required per full chassis (at 120 VAC) (max.)
AC Input Fuse
T15A, 250V (5x20 mm slow-acting 15 amp fuse)
R4300 CAUTION
DOUBLE POLE/NEUTRAL FUSING
Weight
42 lbs empty, 85 lbs with 8 PC blades
Environmental
Rack mounted, 0–35º Celsius (C)
Table 11 Fiber Transceiver Specifications
Connector I/O
16 RJ-45 copper inputs and 16 MT-RJ dual fiber outputs
Fiber Type
62.5 micron, multi-mode, straight-through connection fiber
Max. Distance
62.5 micron: 500 meters (1640 feet) for each C/Port connection
Fiber Signal Loss
Maximum signal attenuation through all fiber runs, patch panels and connectors must
meet the following specification: 62.5 micron fiber: 3.0 dB
Max. Jumper Length
R4300 to Transceiver jumper max. length = 10 meters (33 feet)
Rack Height
1U (1.75 inches) Rack mount kit included
Power Adapter
Dual internal, fully redundant, universal — IEC standard connector
Input 100–240 VAC, 50/60 Hz
Environmental
Stationary installation, 0–35° C ambient temperature