User Manual
Table Of Contents
- 1 Important Safety Instructions
- 2 Introduction
- 3 Installation Overview
- 4 Locating System Components
- 5 Powering System Components
- 6 Wiring System Components
- 6.1 Using RJ-45 connectors
- 6.2 Connecting the matrix frame to a PC running EHX
- 6.3 Connecting the matrix frame to an Ethernet network
- 6.4 Connecting the matrix frame to a PC running Production Maestro Pro
- 6.5 Connecting the matrix frame to user panels
- 6.6 General Purpose Outputs (GPOs)
- 6.7 General Purpose Inputs (GPIs)
- 6.8 E & M signalling with an E-QUE E1 / T1 interface card
- 6.9 Connecting the matrix frame to an external alarm
- 6.10 Connecting to a four-wire audio device
- 6.11 Connecting to interface modules
- 6.11.1 Wiring schemes for the FOR-22 interface module
- 6.11.2 Wiring schemes for the CCI-22 interface module
- 6.11.3 Wiring for Clear-Com analog partyline systems (including Encore)
- 6.11.4 Wiring schemes for TEL-14 interface modules
- 6.11.5 Wiring scheme for the RLY-6 interface module
- 6.11.6 Wiring schemes for a GPI-6 Interface module
- 7 Connecting Matrix Frames
- 8 Glossary

5.2 Powering user panels
5.2.1 V-Series panels
V-Series panels, including expansion panels, have an external DC power supply.
The power supply is universal, operating over a voltage range of 100 - 240 VAC at 50 - 60
Hz. The maximum dissipation is 50W.
5.2.2 I-Series panels
I-Series panels have an internal power supply, with a removable AC power cable.
The power supply is universal, operating over a voltage range of 90 - 245 VAC and
50 - 60 Hz. The maximum dissipation is 40W.
5.3 Powering interface frames
5.3.1 IMF-3
The IMF-3 interface frame requires an external PSU-101 power supply
(see Figure 2: PSU-101 power supply for IMF-3).
Usually, one PSU-101 power supply unit is required for approximately every two IMF-3
frames. This requirement may differ where:
• The IMF-3 is hosting a large number of CCI-22 paryline interface modules,
which require no DC power from the IMF-3 frame (the modules are powered from
the partyline connection).
However, even if the IMF-3 only contains CCI-22 interface modules, a PSU-101
power supply is still required to power the circuitry on the rear panel of the IMF-3.
• The IMF-3 is hosting multiple TEL-14 telephone interface modules. An IMF-3
interface frame can only power eight TEL-14 interfaces on one PSU-101 power
supply. If more TEL-14 interface modules are required, they must be installed in a
second IMF-3 frame with a second power supply.