Installation manual
ClimateMaster Water-Source Heating and Cooling Systems
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Rx (ERV) Module
Rev.: 09/09/08B
IOM
14
Visual observation of the ERV exterior – Check the
following:
❑ Make sure there are no dents, holes, loose screws,
broken hoods, etc. Make a general inspection of the
condition of the exterior.
❑ Make sure all doors are tightly secured.
❑ Make sure all dampers are free to move.
❑ Make sure all hoods, if applicable, are not damaged.
❑ Make sure that the water entrainment fi lter is clean.
❑ Make sure that the ERV/RTU transition is secure.
Visual observation of the ERV interior -
Check the following:
❑
Check that the wheel can move freely. Spin by hand to
insure that nothing is impeding the wheel’s movement.
❑ Check that the wheel is receiving power. With the
door open, push in on the safety switch and insure
that the wheel rotates. The wheels rotate between 40
and 60 rpm.
❑ Check the wheel for dirt. If the wheel or segments
of the wheel are dirty, Clean them using a non-acid
based coil cleaner or alkaline detergent solution.
❑ Check the fi lters. If dirty, replace.
❑
Check the blowers. Insure that the blowers are rotating
in the right direction. Check that the seals around the
doors are not cut, damaged or have holes in them that
would allow water to penetrate into the cabinet.
❑ Check belts for wear and tension. Belts can be
compressed about one-half inch.
❑ Check alignment of the pulleys.
❑ Check that the bushings in the blowers are in place.
❑ Check that the cabinet interior is dry.
ERV Maintenance Check List
CAUTION!
Do not steam clean the ERV wheel segments or subject
them to temperatures above 170°F. High temperatures
or steam will damage the heat exchange surface. Soak
the wheel segments in 140°F or cooler water tempera-
ture for cleaning.