Installation Manual
DUCTING
IO-DV090 IO-DV090
WWW.CLEANCOMFORT.COM
9
It is recommended that a new, separate return duct be
installed for the DV090 from a central area of the house.
If this is not possible, and if the exisng system has
mulple returns, select one to disconnect from the
exisng forced air system and use it for the dedicated
DV090 return. Always select a return from a central
locaon in the home in an area that is always open to
the rest of the home. Do not use a return from a room
that may have its door closed much of the me. If the
home in which the DV090 is to be installed has an
exisng forced air HVAC system, ulize the HVAC
system to make the DV090 installaon easier.
Basement Installation: Install a separate 10" return
to the DV090 in a central area of the home. Oponal:
Duct the supply from the DV090 to a 10" x 10" x 10"
tee/damper, adjusted to 20% open to the basement.
This allows the ability to discharge a variable amount of
dehumidied air into a basement that may not be well
served by the exisng duct system, especially during the
summer months. Duct the other side of the tee to the air
supply of the exisng HVAC system. A backdra damper
is required in the duct between the 10" tee and the
central supply duct to prevent air from being discharged
into the basement during central fan operaon. Connect
a duct from outside to the 6" collar of the DV090 if you
wish to provide venlaon air. See Figure 4.
Fresh Air Ventilation
Venlaon controls determine the me/frequency that
the unit introduces outside air into the structure.
The amount/frequency of venlaon should be based
on the size and occupancy of the residence. If you are
unsure of your venlaon air requirements or have need
for higher air ows, consult Technical Support by calling
1-855-239-2665.
Figure 5: Ac Installaon
Installation in a Basement or Crawlspace
with an Existing Forced Air HVAC System.
Crawlspace Installation: Install a separate return to
the DV090 in a central area of the home. Oponal: Duct
the supply from the DV090 to a 10" x 10" x 10" tee/damper
that is 20% open to the crawlspace if desired. Duct the
other side of the tee to the air supply of the exisng HVAC
system with a backdra damper. Connect an Insulated
duct from outside to the 6" collar of the DV090 if you wish
to provide oponal venlaon air. See Figure 4.
Installation in an Attic with an Existing Forced
Air HVAC System
I
CAUTION!
ALWAYS install a catch pan with a drain or Safety Float
Switch for condensate under the DV090 in an ac
or condensate may damage the living space below.
The Safety Float Switch should be installed in series with
the eld wire that connects the blue (#5) lead from the
DV090 to the blue (#5) lead on the digital control. If over-
ow occurs, this Safety Float Switch opens the compressor
control circuit and stops water producon before the
catch pan overows. The DV090 will connue to venlate
or circulate air as normal, but will not dehumidify unl this
switch closes.
The preferred method of installaon is to create a separate
return for the DV090 in a central area of the structure. Duct
the supply of the DV090 to the air supply of the exisng
HVAC system. Connect an insulated duct from outside to
the 6" collar of the DV090 if you wish to provide fresh make-
up air. Adjust a damper in the duct to provide the desired air
ow. Using the digital control, program the unit to bring in
the desired amount of fresh air. See Figure 5.
Figure 4: Basement or crawlspace installaon.