Humidity Control
The humidity control is an adjustable switch that closes
when the relave humidity of the air in which it is located
rises to the screen set point. The DV090 dehumidier is
equipped with an automac defrost mechanism. If the
dehumidier operates in condions that develop frost
on the evaporator, it will sense the frost build-up and
automacally defrost the evaporator. The dehumidier
may not appear to be operang correctly during the
defrost sequence, but once the defrost sequence is
completed, the unit will resume dehumidifying.
Programmable Ventilation Timer –
DVP-4034748 / DVP-4034753
The venlaon mer controls the impeller fan and the
motorized fresh air damper. When the venlaon mer
is acvated, the dehumidier will circulate the indoor
air, and bring in fresh air from outside. The venlaon
mer should be set for the required venlaon of the
residence. The home should be venlated with fresh air
as suggested by applicable codes and standards.If the
dehumidier fails to venlate as expected, check that the
me on the mer is correct. Also check the programs on
the mer to be sure that the mer is calling for venla-
on at the correct mes
Motorized Ventilation Damper
The motorized venlaon damper is controlled by a eld-
supplied venlaon mer, such as the Clean Comfort
DVP-4034748 control. The damper will open when the
venlaon mer is acvated to allow fresh air into the
home through the 6" diameter fresh air inlet supply duct.
The motorized venlaon damper will remain closed when
the venlaon mer is not acvated to prevent over-venlang
the home when the unit is dehumidifying or recirculang
the indoor air. The motorized venlaon damper operates
on 24VAC from the control circuit.
I
CAUTION!
DO NOT connect high voltage to the damper motor or
damage to the motor may result.
I
CAUTION!
DO NOT force the blade of the damper by hand or
damage to the damper motor may result. The damper
opens in one direcon only. The damper rotates very
slowly; allow sucient me for the damper to cycle.
The damper opens in one direcon only. It rotates very
slowly; be sure to allow sucient me for the damper to
cycle. The damper will take approximately one minute to
cycle from closed to open or from open to closed.
If the motorized venlaon damper fails to operate:
1. Check that the wiring is correct and that voltage is
present at the damper motor.
2. Check for any obstrucon inside the damper. If the
motorized venlaon damper fails to operate aer
performing these checks, it must be replaced.