AE14-5 Series Installation Manual
FILTRATION
FILTRATION
WWW.CLEANCOMFORT.COM
6
IO-AE14-5
INSTALLATION
Figure 5: Air Cleaner
Installaon Locaon
Allow 24 in. (60 cm) clearance for maintaining air cleaner
Allow 6 in. (15 cm) clearance for power box removal.
Installation Location with Humidier
A humidier should be installed in the furnace warm
air duct. However, it may be installed in the return duct
without causing problems to the air cleaner. Care must
be taken to ensure that the humidier does not leak, as
this may cause arcing and a mineral deposit to build up
on the collecng cells.
An atomizing type humidier should be installed
downstream from the air cleaner. If the atomizing type
humidier is installed upstream, high humidity, salts and
minerals may decrease the eciency of the collecng
cells and cause service problems.
If the atomizing type humidier must be installed
upstream, the following precauons should be taken:
1. Atomizing type humidier must be installed as far
from the air cleaner as possible.
2. Collecng cells must be washed frequently to
prevent a mineral deposit build-up.
Installation Location with Air Conditioner
Whenever possible, the air cleaner should be installed
upstream of the cooling coil. This locaon will clean the
air before it reaches the evaporator coil.
Installation Steps
1. Remove exisng equipment lter (if present) and
clean blower compartment: Thoroughly clean the
blower compartment, since your air cleaner can not
remove accumulated dirt from the blower chamber
and distribuon ducts.
2. Open air cleaner access door. Slide lters and
collecng cells out of cabinet.
3. Installing the cabinet: Holes are provided to aach
cabinet to ductwork or equipment. If the adjoining
ductwork is anged, install the screws so that the
screw heads are inside the cabinet. This will help
prevent damage to prelter and carbon VOC lters
during removal for cleaning. Never put screws or
rivets into the removable power box.
4. Transions: If the air duct does not t the air cleaner
opening, a gradual transion is recommended to
reduce air turbulence through the air cleaner and
ensure its ecient operaon. A maximum of 20° of
expansion, or approximately 4 inches per running foot
(10 cm per 30 cm ), is recommended for each side of
the transion ng.
Do not reduce ductwork size to t a smaller
air cleaner. This will increase the velocity of
airow and may decrease cleaning eciency.
5. Turning vanes: If the air cleaner is installed adjacent
to an elbow or angle ng, eld-installed turning
vanes are recommended to improve air distribuon
across the collecng cells.
6. Seal the joints in the return air system: All joints
between the air cleaner, the heang / cooling
equipment and the return air duct should be sealed
to prevent dust from entering the clean air stream.
7. Replace the prelters in the track on the air entering
side of the air cleaner. Place new carbon VOC lters
into the air cleaner. Space lters evenly across the
discharge opening of air cleaner. Never put more
than 3 carbon VOC lters in the air cleaner, as this
may cause a problem with airow.
The collecng cells are placed between the tracks, with
the arrow on cell poinng towards the fan. The cell
handle may need to be reposioned if the airow is in
a dierent direcon than the le to right set up. The
handle should face the door. Close access door.
i
WARNING!
Electrical shock can cause injury or death. Be certain main
line disconnect switch is OFF before wiring.