AE14-5 Series Installation Manual
FILTRATION
FILTRATION
WWW.CLEANCOMFORT.COM
14
TROUBLESH OOTING
IO-AE14-5
Table 5 Troubleshoong Guide
Problem Probable Causes Remedy
Unit does not
funcon correctly.
Power light and
performance
indicator light
are OFF.
System fan is not on. Turn system fan on.
Wiring improperly connected.
Check wiring or verify that plug is inserted in
receptacle and receptacle is powered.
Defecve power switch.
Check power switch for connuity with ohmmeter.
Replace if defecve.
Defecve safety interlock.
Remove door and press safety interlock with a
screwdriver. If lights come on, bend interlock lever
towards front and close door.
Unit does not
funcon correctly.
Power switch light is
ON and performance
indicator light is OFF.
Short in cells due to:
1. Broken ionizing wire.
2. Large parcles wedged between cell plates.
3. Cells washed recently and are sll wet.
4. Cell end plate insulator is dirty or damaged.
5. Cell plate(s) are bent.
1. Remove wire or wire fragments. Replace.
2. Shake large parcles out or wash cell.
3. Allow cells to dry completely.
4. Clean or replace end plate insulator.
5. Straighten plates with pliers.
Defecve performance indicator light.
Determine whether high voltage is present by tesng
power board ② If voltage is present, replace
performance indicator light.
Defecve power board.
Adjust high voltage potenometer on power board
counter-clockwise. If high voltage is not present,
replace power board.
Air Proving Switch (APS) sensor is
burnt out.
Remove power box lid and blow lightly for 10
seconds on APS sensor at boom of power box.
If light does not come on, replace APS.
Air Proving Switch is not geng enough airow
across the sensor.
Check that sensor is located in the plasc bushing
at the front of the power box.
Check that the return duct is installed ush to the
top and front edge of the air cleaner duct opening.
Ensure there is a minimum of 360 CFM of air to
the air cleaner.
O board 24V transformer is not working. Verify output of transformer. Replace if necessary.
Defecve power switch. Verify output of switch. Replace if necessary.
Power switch light is
OFF and performance
indicator light is ON.
Defecve power switch light. Replace power switch.
Cell makes loud
hissing noise
or causes radio
interference.
Internal cell contacts are not touching plates. Test contacts and repair.
Copper contacts on high voltage tray not making
good connecon on cell.
With needle-nose pliers, gently pull contacts down
or replace contacts.