Mounting DC-cables
PAY ATTENTION TO CORRECT POLARITY!
Check that the battery voltage matches the DC input to the inverter (or Combi).
Check the battery poles are clean.
Prepare good electrical contact, use brass or lead battery connectors at the battery
poles.
Connect only one cable at the time.
Start with the Black cable (-). First connect to battery pole, then to inverter (or Combi) (-)
terminal (black).
Double check that Black (-) cable are connected to the correct terminals (-).
Secure there is no risk of short circuit!
Connect Red cable (+). First connect to battery pole, then to inverter (or Combi) (+)
terminal (red).
When connecting the cables a spark will occur. Avoid sparks near the battery!
WARNING!
Do not interchange the battery cables. It will result in instantaneous damage of the unit.
Such damage is not covered by the guarantee.
Do not connect inverters (or Combi) at the AC-output in parallel. It will damage the units.
Such damage is not covered by the guarantee.
Do not connect AC generator or AC mains to the units AC output connector (grey
Neutrik). It will damage the unit. Such damage will not be covered by the guarantee.
3.2.2 AC cables
When installing the AC cables always refer to safety standards valid in the
regarding country
The use of a Residual Current Device (RCD) also known as earth leakage circuit
breaker is highly recommended in any installation
It is also possible to build up a insulated grid and using an insulation monitoring
system to achieve highest protection
Recommended AC cable
The table below gives the minimum recommended wire sizes of the mains cable!
AWG 15 = 1.5mm
2
AWG 17 = 1.0mm
2
Device
type
1012-50 1024-30 1312-80 1512-80 1524-40 2012-100 2324-50
AC cable
17 AWG 17 AWG 15 AWG 15 AWG 15 AWG 15 AWG
15
AWG