Owner's manual

THE CONTINUOUS POWER COMPANY
44
The batteries used in this equipment are recyclable. Proper disposal is required and mandated
by law. The batteries contain lead and pose a hazard to the environment and human health if
not dispose of properly.
Refer to local codes for proper disposal requirements or return the batteries to the factory.
ALWAYS contact the factory for information concerning shipment, disposal, or replacement of
batteries.
Table 15: PREVENTIVE MAINTENANCE SCHEDULE
Item Schedule Actions
Cleaning
6 Mos.
Blow out unit with air.
Battery
6 Mos.
Clean terminals and check for corrosion.
Fans
6 Mos.
Check for proper operation.
5.3 Trouble Analysis
Unit does not power up:
Make sure AC & DC input connectors are connected and seated properly.
Check front panel fuse(F1)
Check Bypass Box for proper installation and wiring.
Check Bypass Box to be switched to the “UPS” position.
No Backup when utility power is lost:
Make sure DC breaker is in the “ON” position.
If Bypass switch is installed, make sure it is in the “UPS” position.
Check Batteries.
Front Panel Fuse(F1) keeps going bad:
Possible bad inverter.
On turn on, Unit goes through startup sequence then goes into alarm and inverter does not turn on:
Possible bad inverter.
Load on unit may be over Max. rating.
Unit in Alarm, but is still operating OK:
Possible over temp.
Check fans in the unit to make sure they are running.
In On-line operation, intersection goes into flash when utility power is loss:
Check UPS for proper installation and wiring.
Options in the program may not be set properly.