User Manual

7
© Copyright 2011. All rights reserved.
The Clarus Environmental Recirculating Media Filter is designed as a secondary treatment device. It works in conjunction with the septic
tank (primary treatment) and the drain eld (water disposal and nal polishing) to provide excellent overall treatment of the onsite efuent.
Refer to the diagram below to see the overall ow of efuent through the system.
Section 2: Pump Discharge System Installation
Figure 3: Pump Discharge Media Filter System Flow Schematic
General System Installation Outline
1. Install septic tank.
2. Install drain line as required to septic tank.
3. Install dosing tank.
4. Install piping between septic tank and dosing tank.
5. Install dosing tank pump.
6. Install wiring from dosing pump to control panel.
7. Install media lter (see detailed instructions below).
8. Install force main from dosing tank to media lter.
9. Install media lter pump.
10. Install wiring from media lter pump to control panel.
11. Install return line from media lter to 80/20 pressure ow splitter.
12. Install 80/20 pressure ow splitter at highest point.
13. Install return line from 80/20 pressure ow splitter to dose tank.
14. Install drain line from 80/20 pressure ow splitter to drain eld.
SK2097B
TO DISPOSAL FIELD
HOUSE
SEWER
20%
80%
PRESSURIZED FLOW
GRAVITY FLOW
SEPTIC
TANK
DOSE
TANK
MEDIA
FILTER
80/20
PRESSURE
FLOW
SPLITTER
W/PUMP
DISCHARGE
CLARUS TIMED
DOSING PANEL
80% RECIRCULATION
20% TO DRAIN
FIELD SYSTEM
80/20
PRESSURE
FLOW
SPLITTER
SEPTIC TANK
DOSE TANK
FORCE MAIN FROM DOSE
TANK TO MEDIA FILTER
SK2229